2113.22 Requirement of a Smoke Test
JUMP TO FULL CODE CHAPTER
A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In lieu thereof, the commissioner may accept the test report of the design professional engineer responsible for the test, which shall be submitted in writing to the department.
To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements:
- The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit.
- If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the requirement of this chapter and the test shall be repeated until the results are satisfactory.
- Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed, and a pressure equivalent to 1/2 inch (12.7 mm) column of water measured at the base of the stack shall be applied. The test shall be conducted for a length of time sufficient to permit the inspection of the chimney.
Related Code Sections
2113.22 Masonry, Requirement of a Smoke Test
determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements ...
2113.22 Masonry, Requirement of a Smoke Test
determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: The ...
2113.22 Masonry, Requirement of a Smoke Test
determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: The ...
503.4.2.4 Chimneys and Vents, Requirement of a Smoke Test
A smoke test shall be conducted in accordance
with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall ...