// CODE SNIPPET
E305.7.1 Required Ventilation
Go To Full Code Chapter
Crawl spaces shall be ventilated by openings through the perimeter wall connecting to the exterior of the foundation. Required vents shall have a combined net free area not less than 1 square inch (0.000645 m2) per 1 square foot (0.0929 m2) of crawl space, and shall conform to the following conditions:
- Openings shall be distributed uniformly around the outside walls of the crawl space.
- Vents shall be fitted with corrosion and decay-resistant wire mesh or grilles with openings not less than 1/4 inch (6 mm) nor more than 1/2 inch (12.7 mm) in size. Vents shall not be fitted with operable louvers, dampers, or other closure mechanisms.
- Plumbing located in a ventilated crawlspace shall be protected from freezing with insulation and/or heat tape.
Related Code Sections
E305.7.1 Florida Standard for Radon-Resistant New Commercial Construction, Required Ventilation
Crawl spaces shall be ventilated by openings through the perimeter wall connecting to the exterior of the foundation. Required vents shall have ...
E305.7.1 Florida Standard for Radon-Resistant New Commercial Construction, Required Ventilation
Crawl spaces shall be ventilated by openings through the perimeter wall connecting to the exterior of the foundation. Required vents shall have ...
1203.2 Interior Environment, Ventilation Required
At least 40 percent and not more than 50 percent of the required venting area is provided by ventilators located in the upper portion of the attic ...
1203.2 Interior Environment, Ventilation Required
At least 40 percent and not more than 50 percent of the required venting area is provided by ventilators located in the upper portion of the attic ...
401.2 Ventilation, Ventilation Required
Every occupied space shall be ventilated by natural means in accordance with Section 402 or by mechanical means in accordance with Section 403. Where ...