The permit holder shall make the applicable tests prescribed in Sections 312.2 through 312.10 to determine compliance with the provisions of this code. The permit holder shall give reasonable advance notice to the code official when the plumbing work is ready for tests. The equipment, material, power and labor necessary for the inspection and test shall be furnished by the permit holder and he or she shall be responsible for determining that the work will withstand the test pressure prescribed in the following tests. Plumbing system piping shall be tested with either water or, for piping systems other than plastic, by air. After the plumbing fixtures have been set and their traps filled with water, the entire drainage system shall be submitted to final tests. The code official shall require the removal of any cleanouts if necessary to ascertain whether the pressure has reached all parts of the system.
312.1.1 Test Gauges
Gauges used for testing shall be as follows:
  1. Tests requiring a pressure of 10 pounds per square inch (psi) (69 kPa) or less shall utilize a testing gauge having increments of 0.10 psi (0.69 kPa) or less.
  2. Tests requiring a pressure of greater than 10 psi (69 kPa) but less than or equal to 100 psi (689 kPa) shall utilize a testing gauge having increments of 1 psi (6.9 kPa) or less.
  3. Tests requiring a pressure of greater than 100 psi (689 kPa) shall utilize a testing gauge having increments of 2 psi (14 kPa) or less.
Upcodes Diagrams

Related Code Sections

105.3 Scope and Administration, Required Testing
Reports of tests shall be retained by the code official for the period required for retention of public records ...
105.3 Scope and Administration, Required Testing
to require tests as evidence of compliance to be made at no expense to the jurisdiction ...
105.3 Scope and Administration, Required Testing
Reports of tests shall be retained by the code official for the period required for retention of public records ...
105.3 Scope and Administration, Required Testing
to require tests as evidence of compliance to be made at no expense to the jurisdiction ...
105.3 Scope and Administration, Required Testing
to require tests as evidence of compliance to be made at no expense to the jurisdiction ...