63.11.4 Required Protection
Go To Full Code Chapter
63.11.4.1 Ventilation
Mechanical ventilation shall be in accordance with the Uniform Mechanical Code and shall comply with all of the following:
- Mechanical ventilation in a room or area shall be at a rate of not less than 1 ft3/min/ft2 (0.00508 m3/s/m2).
- Exhaust shall be taken from a point within 12 in. (305 mm) of the floor.
- The ventilation system shall be designed to operate with a negative pressure in relation to the surrounding area.
63.11.4.2 Emergency Alarm System
Emergency alarm systems shall comply with all of the following:
- Areas where carbon dioxide can accumulate, continuous gas detection shall be provided.
- The system shall be capable of detecting and notifying the building occupants of a gas release of carbon dioxide at, or in excess of, the Time-Weighted Average-Permissible Exposure Limit (TWA-PEL) published by the Occupational Safety and Health Administration (OSHA) and the Threshold Limit Value-Short Term Exposure Limit (TLV®-STEL) published by the American Conference of Governmental Industrial Hygienists (ACGIH). More conservative set points shall be permitted to be used.
- The emergency alarm system activation shall initiate a local alarm within the room or area in which the system is installed.
Upcodes Diagrams
Related Code Sections
63.11.4 Compressed Gases and Cryogenic Fluids, Required Protection
Carbon dioxide storage tanks,
cylinders, piping, and equipment located indoors, in rooms,
and other areas where a leak of carbon dioxide can collect ...
1502.1 Construction Safeguards, Protection Required
Adjoining public and private property shall be protected from damage during construction and demolition work. Protection must be provided ...
1502.1 Construction Safeguards, Protection Required
Adjoining public and private property shall be protected from damage during construction and demolition work. Protection must be provided ...
230.208 Wiring and Protection, Protection Requirements
). Equipment used to protect service-entrance conductors shall meet the requirements of Article 490, Part II ...
230.208 Wiring and Protection, Protection Requirements
). Equipment used to protect service-entrance conductors shall meet the requirements of Article 490, Part II ...