UpCodes logo
Go To Full Code Chapter
Piping systems shall be designed and sized to deliver the required flow rates at the utilization pressures. [NFPA 99:5.1.10.11.1.1]
1323.1.1 Mains and Branches
Mains and branches in medical gas piping systems shall be not less than DN15 (NPS 1/2) (5/8 inch O.D.) size. Mains and branches in medical-surgical vacuum systems shall be not less than DN20 (NPS 3/4) (7/8 inch O.D.) size. [NFPA 99:5.1.10.11.1.2, 5.1.10.11.1.3]
1323.1.2 Drops to Individual Stations
Drops to individual station outlets and inlets shall be not less than DN15 (NPS 1/2) (5/8 inch O.D.) size. [NFPA 99:5.1.10.11.1.4]
1323.1.3 Runouts and Connecting Tubing
Runouts to alarm panels and connecting tubing for gauges and alarm devices shall be permitted to be DN8 (NPS 1/4) (3/8 inch O.D.) size. [NFPA 99:5.1.10.11.1.5]
Upcodes Diagrams
See More

Related Code Sections

1215.0 Fuel Gas Piping, Required Gas Piping Size
in Figure 1215.1.1) FIGURE 1215.1.1 EXAMPLE ILLUSTRATING USE OF TABLE 1208.4.1 AND TABLE 1215.2(1) Problem: Determine the required pipe size of each ...
1215.6 Fuel Gas Piping, Variable Gas Pressure
) of water column, or where diversity demand factors are used, the design, pipe, sizing, materials, location, and use of such systems first shall ...
1215.1.1 Fuel Gas Piping, Longest Length Method
1208.4.1 AND TABLE 1215.2(1) Problem: Determine the required pipe size of each section and outlet of the piping system shown in Figure 1215.1.1. Gas ...