Medical gas and vacuum systems shall be capable of delivering service in the pressure ranges listed in Table 1305.1.
TABLE 1305.1
STANDARD DESIGNATION COLORS AND OPERATING PRESSURES FOR GAS AND VACUUM SYSTEMS
[NFPA 99: TABLE 5.1.11]
GAS SERVICE ABBREVIATED NAME COLORS (BACKGROUND/TEXT) STANDARD GAUGE PRESSURE
Medical air Med Air Yellow/black 50—55 psi
Carbon dioxide CO2 Gray/black or gray/white 50—55 psi
Helium He Brown/white 50—55 psi
Nitrogen N2 Black/white 160—185 psi
Nitrous oxide N2O Blue/white 50—55 psi
Oxygen O2 Green/white or white/green 50—55 psi
Oxygen/carbon dioxide mixtures O2/CO2 n% (n = % of CO2) Green/white 50—55 psi
Medical-surgical vacuum Med Vac White/black 15 inch to 30 inch HgV
Waste anesthetic gas disposal WAGD Violet/white Varies with system type
Other mixtures Gas A% / Gas B% Colors as above; major gas for background/minor gas for text None
Nonmedical air (Category 3 gas-powered device) Yellow-and-white diagonal stripe/black None
Nonmedical and Category 3 vacuum White-and-black diagonal stripe/black boxed None
Laboratory air Yellow-and-white checker board/black None
Laboratory vacuum White-and-black checkerboard/black boxed None
Instrument air Red/white 160—185 psi
For SI units: 1 pound-force per square inch = 6.8947 kPa, 1 inch of mercury vacuum (HgV) = 3.386 kPa