29.8.2 Required Occupant Notification
Go To Full Code Chapter
29.8.2.1
Fire-warning equipment used to provide required or optional detection shall produce audible fire alarm signals that comply with 29.8.2.1.1 or 29.8.2.1.2.
29.8.2.1.1* Interconnected Smoke and Heat Alarms
For other than mechanically powered single-station heat alarms and unless exempted by applicable laws, codes, or standards, smoke or heat alarms used to provide a fire-warning function, and where two or more alarms are installed within a dwelling unit, suite of rooms, or similar area, shall be arranged so that the operation of any smoke or heat alarm causes all alarms within these locations to sound.
29.8.2.1.2 Household Fire Alarm System
Where a household fire alarm system is used to provide a fire-warning function, notification appliances shall be installed to meet the performance requirements of 29.5.7.
29.8.2.2*
Unless otherwise permitted by the authority having jurisdiction, audible fire alarm signals shall sound only in an individual dwelling unit, suite of rooms, or similar area and shall not be arranged to operate fire-warning equipment or fire alarm systems outside these locations.
29.8.2.3
Remote annunciation shall be permitted.
Related Code Sections
29.5.2 Single- And Multiple-Station Alarms and Household Fire Alarm Systems, Required Occupant Notification
, notification appliances shall be installed to meet the performance requirements of 29.3.6 ...
29.8.2 Single- And Multiple-Station Alarms and Household Signaling Systems, Required Occupant Notification
Fire-warning equipment used to provide required or optional detection shall produce audible fire alarm signals that comply with 29.8.2.1.1 ...
29.5.2.1 Single- And Multiple-Station Alarms and Household Fire Alarm Systems,
, notification appliances shall be installed to meet the performance requirements of 29.3.6 ...
29.5.2.1.2 Single- And Multiple-Station Alarms and Household Fire Alarm Systems, Household Fire Alarm System
Where a household fire alarm system is used to provide a fire-warning function, notification appliances shall be installed to meet the performance ...
29.5.2.1.1* Single- And Multiple-Station Alarms and Household Fire Alarm Systems, Smoke and Heat Alarms
alarms within these locations to sound. Exception: The arrangement for all alarms to sound shall not be required for mechanically powered single-station ...