2702.4 Required Loads for Optional Standby Power Systems
Go To Full Code Chapter
In addition to any other loads, optional standby power systems shall be capable of providing power to the following standby and emergency power loads upon failure of the normal power supply:
- Emergency lighting;
- Fire alarm systems; and
- Elevators as follows:
- For Group R-2 occupancies in buildings greater than 125 feet (38 100 mm) in height, at least one elevator serving all floors, or one elevator per bank where different banks serve different portions of the building; or
- For all other buildings having occupied floors located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access, at least one elevator that serves all floors.
2702.4.1 Additional Optional Standby Power Systems
2702.4.2 Compliance With NFPA 110 and UL 2200
Where an optional standby power system is required to supply emergency or required standby power loads, such power system shall comply with the UL 2200 listing and NFPA 110.
2702.4.3 Special Inspection
Where an optional standby power system is required to supply emergency or required standby power loads, such power system shall be subject to special inspection in accordance with Section 1704.31 and the rules of the department.
Upcodes Diagrams
Related Code Sections
2702.4 Electrical, Required Loads for Optional Standby Power Systems
emergency or required standby power loads, any additional optional standby power system need not supply power to such emergency or required standby ...
2702.4 Electrical, Required Loads for Optional Standby Power Systems
In addition to any other loads, optional standby power systems shall be capable of providing power to the following systems upon failure ...
2702.4 Electrical, Required Loads for Optional Standby Power Systems
In addition to any other loads, optional standby power systems shall be capable of providing power to the following systems upon failure ...
2702.1.7 Electrical, Automatic Transfer Devices and Power System Feeders
system feeders that serve emergency and required standby power system equipment shall not be located in the same room as the emergency power system ...
2702.1 Electrical, Installation
with optional standby loads as a common system, may share common fuel supplies and other common equipment and systems ...