The building official, upon notification, shall make the inspections set forth in Sections 110.3.1 through 110.3.12.
[A] 110.3.1 Footing and Foundation Inspection
Footing and foundation inspections shall be made after excavations for footings are complete and any required reinforcing steel is in place. For concrete foundations, any required forms shall be in place prior to inspection. Materials for the foundation shall be on the job, except where concrete is ready mixed in accordance with ASTM C94, the concrete need not be on the job.
[A] 110.3.2 Concrete Slab and Under-Floor Inspection
Concrete slab and under-floor inspections shall be made after in-slab or under-floor reinforcing steel and building service equipment, conduit, piping accessories and other ancillary equipment items are in place, but before any concrete is placed or floor sheathing installed, including the subfloor.
[A] 110.3.3 Lowest Floor Elevation
In flood hazard areas, upon placement of the lowest floor, including the basement, and prior to further vertical construction, the elevation certification required in Section 1612.4 or the International Residential Code, as applicable, shall be submitted to the building official.
[A] 110.3.4 Frame Inspection
Framing inspections shall be made after the roof deck or sheathing, all framing, fire-blocking and bracing are in place and pipes, chimneys and vents to be concealed are complete and the rough electrical, plumbing, heating wires, pipes and ducts are approved.
[A] 110.3.5 Types IV-A, IV-B and IV-C Connection Protection Inspection
In buildings of Types IV-A, IV-B and IV-C construction, where connection fire-resistance ratings are provided by wood cover calculated to meet the requirements of Section 2304.10.1, inspection of the wood cover shall be made after the cover is installed, but before any other coverings or finishes are installed.
[A] 110.3.6 Lath, Gypsum Board and Gypsum Panel Product Inspection
Lath, gypsum board and gypsum panel product inspections shall be made after lathing, gypsum board and gypsum panel products, interior and exterior, are in place, but before any plastering is applied or gypsum board and gypsum panel product joints and fasteners are taped and finished.
Exception: Gypsum board and gypsum panel products that are not part of a fire-resistance-rated assembly or a shear assembly.
[A] 110.3.7 Weather-Exposed Balcony and Walking Surface Waterproofing
Where balconies or other elevated walking surfaces have weather-exposed surfaces, and the structural framing is protected by an impervious moisture barrier, all elements of the impervious moisture barrier system shall not be concealed until inspected and approved.
Exception: Where special inspections are provided in accordance with Section 1705.1.1, Item 3.
[A] 110.3.8 Fire- And Smoke-Resistant Penetrations
Protection of joints and penetrations in fire-resistance-rated assemblies, smoke barriers and smoke partitions shall not be concealed from view until inspected and approved.
[A] 110.3.9 Energy Efficiency Inspections
Inspections shall be made to determine compliance with Chapter 13 and shall include, but not be limited to, inspections for: envelope insulation R- and U-values, fenestration U-value, duct system R-value, and HVAC and water-heating equipment efficiency.
[A] 110.3.10 Other Inspections
In addition to the inspections specified in Sections 110.3.1 through 110.3.9, the building official is authorized to make or require other inspections of any construction work to ascertain compliance with the provisions of this code and other laws that are enforced by the department of building safety.
[A] 110.3.11 Special Inspections
[A] 110.3.12 Final Inspection
The final inspection shall be made after all work required by the building permit is completed.
[A] 110.3.12.1 Flood Hazard Documentation
If located in a flood hazard area, documentation of the elevation of the lowest floor as required in Section 1612.4 shall be submitted to the building official prior to the final inspection.
Upcodes Diagrams

Related Code Sections

109.3 Scope and Administration, Required Inspections
are complete and any required reinforcing steel is in place. For concrete foundations, any required forms shall be in place prior to inspection. Materials ...
109.3 Scope and Administration, Required Inspections
are complete and any required reinforcing steel is in place. For concrete foundations, any required forms shall be in place prior to inspection. Materials ...
110.3 Scope and Administration, Required Inspections
are complete and any required reinforcing steel is in place. For concrete foundations, any required forms shall be in place prior to inspection ...
110.3 Scope and Administration, Required Inspections
are complete and any required reinforcing steel is in place. For concrete foundations, any required forms shall be in place prior to inspection ...