5704.2.9.2.1 Required Foam Fire Protection Systems
Go To Full Code Chapter
Where required by the fire code official, foam fire protection shall be provided for above-ground tanks, other than pressure tanks operating at or above 1 pound per square inch gauge (psig) (6.89 kPa) where such tank, or group of tanks spaced less than 50 feet (15 240 mm) apart measured shell to shell, has a liquid surface area in excess of 1,500 square feet (139 m2), and is in accordance with one of the following:
- Used for the storage of Class I or II liquids.
- Used for the storage of crude oil.
- Used for in-process products and is located within 100 feet (30 480 mm) of a fired still, heater, related fractioning or processing apparatus or similar device at a processing plant or petroleum refinery as herein defined.
- Considered by the fire code official as posing an unusual exposure hazard because of topographical conditions; nature of occupancy, proximity on the same or adjoining property, and height and character of liquids to be stored; degree of private fire protection to be provided; and facilities of the fire department to cope with flammable liquid fires.
Related Code Sections
5704.2.9.2.1 Flammable and Combustible Liquids, Required Foam Fire Protection Systems
Where required by the fire code official, foam fire protection shall be provided for above-ground tanks, other than pressure tanks operating ...
5704.2.9.2.1 Flammable and Combustible Liquids, Required Foam Fire Protection Systems
Where required by the fire code official, foam fire protection shall be provided for above-ground tanks, other than pressure tanks operating ...
22.29.1 Special Occupancy Requirements, Design Requirements
protection designed for a density of 0.25 gpm/ft2 (10.2 mm/min) over the fire area or compressed air foam systems should be considered for hydraulic ...
22.29.1 Special Occupancy Requirements, Design Requirements
sprinkler protection designed for a density of 0.25 gpm/ft2 (10.2 mm/min) over the fire area or compressed air foam systems should be considered for hydraulic ...
26.35.1 Special Occupancy Requirements, Design Requirements
suppression systems in 26.35.1.3.1 shall include the simultaneous operation of all fire protection systems associated with a single (multicell) train ...