8.6.5* Required Fire Resistance Rating
Go To Full Code Chapter
The minimum fire resistance rating for the enclosure of floor openings shall be as follows (see 7.1.3.2.1 for enclosure of exits):
- Enclosures connecting four or more stories in new construction — 2-hour fire barriers
- Other enclosures in new construction — 1-hour fire barriers
- Existing enclosures in existing buildings — 1/2-hour fire barriers
- Enclosures for lodging and rooming houses — as specified in Chapter 26
- Enclosures for new hotels — as specified in Chapter 28
- Enclosures for new apartment buildings — as specified in Chapter 30
Related Code Sections
8.6.5* Features of Fire Protection, Required Fire Resistance Rating
The minimum fire resistance rating for the enclosure of floor openings shall be as follows (see 7.1.3.2.1 for enclosure of exits): Enclosures ...
705.5 Fire and Smoke Protection Features, Fire-Resistance Ratings
Exterior walls shall be fire-resistance rated in accordance with Tables 601 and 602 and this section. The required fire-resistance rating of exterior ...
707.5.1 Fire and Smoke Protection Features, Supporting Construction
The supporting construction for a fire barrier shall be protected to afford the required fire-resistance rating of the fire barrier supported. Hollow ...
711.2.3 Fire and Smoke Protection Features, Supporting Construction
The supporting construction shall be protected to afford the required fire-resistance rating of the horizontal assembly supported. Exception: In ...
704.4 Fire and Smoke Protection Features, Protection of Secondary Members
Secondary members that are required to have protection to achieve a fire-resistance rating shall be protected by individual encasement protection ...