Every system shall include the following documentation, which shall be delivered to the owner or the owner's representative upon final acceptance of the system:
  1. Owner's manual including a complete set of operations and maintenance manuals, manufacturer's published instructions, and product data sheets covering all system equipment
  2. Record and as-built drawings
  3. Written sequence of operation
  4. One current copy of the record of completion form, updated to reflect all system additions or modifications
  5. For software-based systems, a record copy of the system-specific software
  6. Copy of the site-specific software stored on-site in nonvolatile, nonerasable, nonrewritable memory
  7. Emergency response plan, with operational management procedures defined for management and activation of the system
  8. Risk analysis, when provided