401.4.1 Required Dampers in Intake Openings

NYC Mechanical Code 2014 > 4 Ventilation > 401 General > 401.4 Intake Opening Location > 401.4.1 Required Dampers in Intake Openings
JUMP TO FULL CODE CHAPTER
An outdoor air intake opening with gross area of more than 144 square inches (0.0929 m2) shall be provided with fire dampers and smoke dampers, or combined fire and smoke dampers when such opening is located as follows:

1. Less than 30 feet (9144 mm) above grade.

2. Less than 30 feet (9144 mm) in any direction from any opening in another building.

3. Less than 15 feet (4572 mm) from a lot line.

4. Less than 50 feet (15 240 mm) above and less than 50 feet (15 240 mm) in any direction from a roof constructed of combustible material or a building in which the exterior walls are constructed wholly or partly of wood.

5. Where fire dampers are required by Section 607.5.6.

Exceptions:

1. Smoke dampers shall not be required for outdoor air intake openings installed in any construction required to have a fire-resistance rating that is less than 2 hours.

2. Smoke dampers shall not be required for outdoor air intake openings of systems greater than 15,000 cfm (7.1 m3/s) which are provided with smoke dampers in accordance with Chapter 6 of this code and arranged so as to not introduce smoke into the building or space in which the equipment is located.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


401.4.1 Ventilation, Required Dampers in Intake Openings
Smoke dampers shall not be required for outdoor air intake openings of systems greater than 15,000 cfm (7.1 m 3 /s) which are provided with smoke dampers ...
NYC Mechanical Code 2014 > 4 Ventilation > 401 General > 401.4 Intake Opening Location > 401.4.1 Required Dampers in Intake Openings
401.5.1 Ventilation, Intake Openings
the exterior walls are constructed wholly or partly of wood. Exceptions: 1. Smoke dampers shall not be required for outdoor air intake ...
NYC Mechanical Code 2008 > 4 Ventilation > 401 General > 401.5 Opening Location > 401.5.1 Intake Openings
Reference Standard 13 Mechanical Ventilation, Air Conditioning, and Refrigeration Systems [PDF] (page 4)
Exception No. 1: Smoke dampers shall not be required for outdoor air intake openings installed in any construction required to have a fire resistance rating ...
NYC 1968 Code (Vol II) [PDF] > Systems Reference Standard 13 Mechanical Ventilation, Air Conditioning, and Refrigeration Systems
C403.2.4.4 Commercial Energy Efficiency, Shutoff Dampers
Stairway and shaft vent dampers shall meet the requirements of Section C403.2.4.4.1. Outdoor air supply intakes and exhausts meet the requirements ...
NYC Energy Code 2014 > C4 Commercial Energy Efficiency > C403 Building Mechanical Systems > C403.2 Provisions Applicable to All Mechanical Systems (Mandatory) > C403.2.4 HVAC System Controls > C403.2.4.4 Shutoff Dampers
Appendix CA Modified National Standard for Buildings, except for Low-Rise Residential Buildings [PDF] (page 61)
dampers that are capable of being automatically closed during normal building operation and are interlocked to open as required by fire and smoke ...
NYC Energy Code 2016 [PDF] > CA Modified National Standard for Buildings, except for Low-Rise Residential Buildings
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Contact Careers Terms Privacy
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US