401.4.1 Required Dampers in Intake Openings
Related Code Sections
401.4.1 Ventilation, Required Dampers in Intake Openings
An outdoor air intake opening with gross area of more than 144 square inches (0.0929 m 2 ) shall be provided with fire dampers and smoke dampers ...
NYC Mechanical Code 2014 > 4 Ventilation > 401 General > 401.4 Intake Opening Location > 401.4.1 Required Dampers in Intake Openings
401.4.1 Ventilation, Required Dampers in Intake Openings
Outdoor air intakes shall be provided with dampers in accordance with Chapter 6 ...
NYC Mechanical Code 2022 > 4 Ventilation > 401 General > 401.4 Intake Opening Location > 401.4.1 Required Dampers in Intake Openings
401.5.1 Ventilation, Intake Openings
are constructed wholly or partly of wood.
Exceptions:
Smoke dampers shall not be required for outdoor air intake openings installed in any ...
NYC Mechanical Code 2008 > 4 Ventilation > 401 General > 401.5 Opening Location > 401.5.1 Intake Openings
607.5.6.1 Duct Systems, Outdoor Air Intake Openings
, or combined fire and smoke dampers when such opening is located as follows (intake and exhaust separation requirements of Chapters 4 and 5 shall also ...
NYC Mechanical Code 2022 > 6 Duct Systems > 607 Ducts and Air Transfer Openings > 607.5 Where Required > 607.5.6 Exterior Walls > 607.5.6.1 Outdoor Air Intake Openings
Reference Standard 13 Mechanical Ventilation, Air Conditioning, and Refrigeration Systems [PDF] (page 4)
Exception No. 1: Smoke dampers shall not be required for outdoor air intake openings installed in any construction required to have a fire resistance rating ...
NYC 1968 Code (Vol II) [PDF] > Reference Standard 13 Mechanical Ventilation, Air Conditioning, and Refrigeration Systems