• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

Section 120.2 Required Controls for Space-Conditioning Systems

California Energy Code 2019 > 3 Nonresidential, High-Rise Residential Hotel/Motel Occupancies, and Covered Processes — Mandatory Requirements > 120.2 Required Controls for Space-Conditioning Systems
JUMP TO FULL CODE CHAPTER
Nonresidential, high-rise residential, and hotel/motel buildings shall comply with the applicable requirements of Sections 120.2(a) through 120.2(k).

(a) Thermostatic controls for each zone. The supply of heating and cooling energy to each space-conditioning zone or dwelling unit shall be controlled by an individual thermostatic control that responds to temperature within the zone and that meets the applicable requirements of Section 120.2(b). An energy management control system (EMCS) may be installed to comply with the requirements of one or more thermostatic controls if it complies with all applicable requirements for each thermostatic control.
Exception to Section 120.2(a): An independent perimeter heating or cooling system may serve more than one zone without individual thermostatic controls if:
  1. All zones are also served by an interior cooling system; and
  2. The perimeter system is designed solely to offset envelope heat losses or gains; and
  3. The perimeter system has at least one thermostatic control for each building orientation of 50 feet or more; and
  4. The perimeter system is controlled by at least one thermostat located in one of the zones served by the system.


(b) Criteria for zonal thermostatic controls. The individual thermostatic controls required by Section 120.2(a) shall meet the following requirements as applicable:
  1. Where used to control comfort heating, the thermostatic controls shall be capable of being set, locally or remotely, down to 55°F or lower.
  2. Where used to control comfort cooling, the thermostatic controls shall be capable of being set, locally or remotely, up to 85°F or higher.
  3. Where used to control both comfort heating and comfort cooling, the thermostatic controls shall meet Items 1 and 2 and shall be capable of providing a temperature range or dead band of at least 5°F within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum.
    Exception 1 to Section 120.2(b)3: Systems with thermostats that require manual changeover between heating and cooling modes.
    Exception 2 to Section 120.2(b)3: Systems serving healthcare facilities.
  4. Thermostatic controls for all single zone, air conditioners and heat pumps shall comply with the requirements of Sections 110.2(c) and 110.12(a) and, if equipped with DDC to the Zone level, with the Automatic Demand Shed Controls of Section 110.12(b).
    Exception 1 to Section 120.2(b)4: Systems serving exempt process loads that must have constant temperatures to prevent degradation of materials, a process, plants or animals.
    Exception 2 to Section 120.2(b)4: Package terminal air conditioners, package terminal heat pumps, room air conditioners and room air conditioner heat pumps.
    Exception 3 to Section 120.2(b)4: Systems serving healthcare facilities.


(c) Hotel/motel guest room and high-rise residential dwelling unit thermostats.
  1. Hotel/motel guest room thermostats shall:
    1. Have numeric temperature setpoints in °F and °C; and
    2. Have setpoint stops, which are accessible only to authorized personnel, such that guest room occupants cannot adjust the setpoint more than ±5°F (±3°C); and
    3. Meet the requirements of Section 110.2(c).
      Exception to Section 120.2(c)1: Thermostats that are integrated into the room heating and cooling equipment.
  2. High-rise residential dwelling unit thermostats shall meet the requirements of Section 110.2(c).

(d) Heat pump controls. All heat pumps with supplementary electric resistance heaters shall be installed with controls that comply with Section 110.2(b).

(e) Shut-off and reset controls for space-conditioning systems. Each space-conditioning system shall be installed with controls that comply with the following:
  1. The control shall be capable of automatically shutting off the system during periods of nonuse and shall have:
    1. An automatic time switch control device complying with Section 110.9(c), with an accessible manual override that allows operation of the system for up to 4 hours; or
    2. An occupancy sensor; or
    3. A 4-hour timer that can be manually operated.
      Exception to Section 120.2(e)1: Mechanical systems serving retail stores and associated malls, restaurants, grocery stores, churches and theaters equipped with 7-day programmable timers.
  2. The control shall automatically restart and temporarily operate the system as required to maintain:
    1. A setback heating thermostat setpoint if the system provides mechanical heating; and
      Exception to Section 120.2(e)2A: Thermostat setback controls are not required in nonresidential buildings in areas where the Winter Median of Extremes outdoor air temperature determined in accordance with Section 140.4(b)3 is greater than 32°F.
    2. A setup cooling thermostat setpoint if the system provides mechanical cooling.
      Exception to Section 120.2(e)2B: Thermostat setup controls are not required in nonresidential buildings in areas where the Summer Design Dry Bulb 0.5 percent temperature determined in accordance with Section 140.4(b)3 is less than 100°F.
  3. Occupancy sensing zone controls. Space conditioning systems serving room(s) that are required to have occupant sensing controls in accordance with Section 130.1(c), and where the Table 120.1-A occupancy category permits ventilation air to be reduced to zero when the space is in occupied-standby mode, shall meet the following:
    1. The zone shall be placed in occupied standby mode when all room(s) served by the zone are unoccupied for more than 5 minutes; and
    2. During occupied standby mode.
      1. Automatically set up the operating cooling temperature set point by 2°F or more and set back the operating heating temperature set point by 2°F or more; or
      2. For multiple zone systems with Direct Digital Controls (DDC) to the zone level, setup the operating cooling temperature setpoint by 0.5°F or more and setback the operating heating temperature setpoint by 0.5°F or more.
    3. During occupied-standby mode, all airflow to the zone shall be shut off whenever the space temperature is between the active heating and cooling set-points.
      Exception 1 to Sections 120.2(e)1, 2, 3: Where it can be demonstrated to the satisfaction of the enforcing agency that the system serves an area that must operate continuously.
      Exception 2 to Sections 120.2(e)1, 2, 3: Systems with full load demands of 2 kW or less, if they have a readily accessible manual shut-off switch.
      Exception 3 to Sections 120.2(e) 1 and 2: Systems serving hotel/motel guest rooms, if they have a readily accessible manual shut-off switch.
  4. Hotel and motel guest rooms shall have captive card key controls, occupancy sensing controls or automatic controls such that, no longer than 30 minutes after the guest room has been vacated, setpoints are set up at least +5°F (+3°C) in cooling mode and set down at least -5°F (-3°C) in heating mode.
    Exception to Section 120.2(e): Systems serving healthcare facilities.


(f) Dampers for air supply and exhaust equipment. Outdoor air supply and exhaust equipment shall be installed with dampers that automatically close upon fan shutdown.
Exception 1 to Section 120.2(f): Equipment that serves an area that must operate continuously.
Exception 2 to Section 120.2(f): Gravity and other non-electrical equipment that has readily accessible manual damper controls.
Exception 3 to Section 120.2(f): At combustion air intakes and shaft vents.
Exception 4 to Section 120.2(f): Where prohibited by other provisions of law.


(g) Isolation area devices. Each space-conditioning system serving multiple zones with a combined conditioned floor area of more than 25,000 square feet shall be designed, installed and controlled to serve isolation areas.
  1. Each zone, or any combination of zones not exceeding 25,000 square feet, shall be a separate isolation area.
  2. Each isolation area shall be provided with isolation devices, such as valves or dampers, that allow the supply of heating or cooling to be reduced or shut off independently of other isolation areas.
  3. Each isolation area shall be controlled by a device meeting the requirements of Section 120.2(e)1.
    Exception to Section 120.2(g): Zones designed to be conditioned continuously.


(h) Automatic demand shed controls. See Section 110.12 for requirements for automatic demand shed controls.


(i) Economizer fault detection and diagnostics (FDD). All newly installed air handlers with a mechanical cooling capacity greater than 54,000 Btu/hr and an installed air economizer shall include a stand-alone or integrated Fault Detection and Diagnostics (FDD) system in accordance with Subsections 120.2(i)1 through 120.2(i)8.
  1. The following temperature sensors shall be permanently installed to monitor system operation: outside air, supply air, and when required for differential economizer operation a return air sensor, and
  2. Temperature sensors shall have an accuracy of ±2°F over the range of 40°F to 80°F; and
  3. The controller shall have the capability of displaying the value of each sensor; and
  4. The controller shall provide system status by indicating the following conditions:
    1. Free cooling available;
    2. Economizer enabled;
    3. Compressor enabled;
    4. Heating enabled, if the system is capable of heating; and
    5. Mixed-air low limit cycle active.
  5. The unit controller shall allow manual initiation of each operating mode so that the operation of cooling systems, economizers, fans and heating system can be independently tested and verified; and
  6. Faults shall be reported in one of the following ways:
    1. Reported to an Energy Management Control System regularly monitored by facility personnel.
    2. Annunciated locally on one or more zone thermostats, or a device within five (5) feet of zone thermostat(s), clearly visible, at eye level, and meeting the following requirements:
      1. On the thermostat, device, or an adjacent written sign, display instructions to contact appropriate building personnel or an HVAC technician; and
      2. In buildings with multiple tenants, the annunciation shall either be within property management offices or in a common space accessible by the property or building manager.
    3. Reported to a fault management application which automatically provides notification of the fault to a remote HVAC service provider.
  7. The FDD system shall detect the following faults:
    1. Air temperature sensor failure/fault;
    2. Not economizing when it should;
    3. Economizing when it should not;
    4. Damper not modulating; and
    5. Excess outdoor air.
  8. The FDD System shall be certified by the Energy Commission as meeting requirements of Subsections 120.2(i)1 through 120.2(i)7 in accordance with Section 110.0 and JA6.3.
    Exception to 120.2(i)8: FDD algorithms based in direct digital control systems are not required to be certified to the Energy Commission.


(j) Direct Digital Controls (DDC). Direct Digital Controls to the zone shall be provided as specified by Table 120.2-A.
The provided DDC system shall meet the control logic requirements of Sections 120.1(d) and 120.2(h), and be capable of the following:
  1. Monitoring zone and system demand for fan pressure, pump pressure, heating and cooling;
  2. Transferring zone and system demand information from zones to air distribution system controllers and from air distribution systems to heating and cooling plant controllers;
  3. Automatically detecting the zones and systems that may be excessively driving the reset logic and generate an alarm or other indication to the system operator;
  4. Readily allow operator removal of zones(s) from the reset algorithm;
  5. For new buildings, trending and graphically displaying input and output points; and
  6. Resetting heating and cooling setpoints in all noncritical zones upon receipt of a signal from a centralized contact or software point as described in Section 120.2(h).


(k) Optimum start/stop controls. Space conditioning systems with DDC to the zone level shall have optimum start/stop controls. The control algorithm shall, as a minimum, be a function of the difference between space temperature and occupied setpoint, the outdoor air temperature, and the amount of time prior to scheduled occupancy. Mass radiant floor slab systems shall incorporate floor temperature onto the optimum start algorithm.
Exception to Section 120.2(k): Systems that must operate continuously.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, and 25943, Public Resources Code.

TABLE 120.2-A
DDC APPLICATIONS AND QUALIFICATIONS
BUILDING STATUS APPLICATIONS QUALIFICATIONS
Newly Constructed Buildings Air handling system and all zones served by the system Individual systems supplying more than three zones and with design heating or cooling capacity of 300 kBtu/h and larger
Chilled water plant and all coils and terminal units served by the system Individual plants supplying more than three zones and with design cooling capacity of 300 kBtu/h (87.9 kW) and larger
Hot water plant and all coils and terminal units served by the system Individual plants supplying more than three zones and with design heating capacity of 300 kBtu/h (87.9 kW) and larger
Additions or Alterations Zone terminal unit such as VAV box Where existing zones served by the same air handling, chilled water, or hot water systems that have DDC
Air handling system or fan coil Where existing air handling system(s) and fan coil(s) served by the same chilled or hot water plant have DDC
New air handling system and all new zones served by the system Individual systems with design heating or cooling capacity of 300 kBtu/h and larger and supplying more than three zones and more than 75 percent of zones are new
New or upgraded chilled water plant Where all chillers are new and plant design cooling capacity is 300 kBtu/h (87.9 kW) and larger
New or upgraded hot water plant Where all boilers are new and plant design heating capacity is 300 kBtu/h (87.9 kW) and larger

Related Code Sections


Section 120.2 Nonresidential, High-Rise Residential Hotel/Motel Occupancies, and Covered Processes — Mandatory Requirements, Required Controls for Space-Conditioning Systems
Occupancy sensing zone controls. Space conditioning systems serving room(s) that are required to have occupant sensing controls in accordance with Section ...
California Energy Code 2019 > 3 Nonresidential, High-Rise Residential Hotel/Motel Occupancies, and Covered Processes — Mandatory Requirements > 120.2 Required Controls for Space-Conditioning Systems
Section 120.2 Nonresidential, High-Rise Residential Hotel/Motel Occupancies, and Covered Processes—Mandatory Requirements, Required Controls for Space- Conditioning Systems
) Shut-off and reset controls for space-conditioning systems. Each space-conditioning system shall be installed with controls that comply ...
California Energy Code 2016 > 3 Nonresidential, High-Rise Residential Hotel/Motel Occupancies, and Covered Processes—Mandatory Requirements > 120.2 Required Controls for Space- Conditioning Systems
A5.207.5 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4], Controls for Space-Conditioning Systems
Space-conditioning systems shall be installed with controls that comply with the applicable requirements of Subsections A5.207.5.1 through A5.207.5.5 ...
California Green Building Standards Code 2016 > A6.1 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4] > A5.207 [OSHPD 1, 2 & 4] HVAC Design, Equipment and Installation > A5.207.5 Controls for Space-Conditioning Systems
A5.207.5 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4], Controls for Space-Conditioning Systems
Space-conditioning systems shall be installed with controls that comply with the applicable requirements of Subsections A5.207.5.1 through A5.207.5.5 ...
California Green Building Standards Code 2019 > A6.1 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4] > A5.207 [OSHPD 1, 2 & 4] HVAC Design, Equipment and Installation > A5.207.5 Controls for Space-Conditioning Systems
909.17 Fire Protection Systems, System Response Time
equipment and smoke control system startup, shall allow for full operational mode to be achieved before the conditions in the space exceed the design ...
California Building Code 2016 (Vol 1 & 2) > 9 Fire Protection Systems > 909 Smoke Control Systems > 909.17 System Response Time
Help Contact Us Privacy Terms
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code Compare
Code Compare
Highlight differences between any two building codes.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING