[A] 105.6 Required Construction Permits
JUMP TO FULL CODE CHAPTER
The fire code official is authorized to issue construction permits for work as set forth in Sections 105.6.1 through 105.6.24.
A construction permit is required for installation of or modification to an automatic fire-extinguishing system. Maintenance performed in accordance with this code is not considered to be a modification and does not require a permit.
Where the compressed gases in use or storage exceed the amounts listed in Table 105.5.9, a construction permit is required to install, repair damage to, abandon, remove, place temporarily out of service, or close or substantially modify a compressed gas system.
Exceptions:
- Routine maintenance.
- For emergency repair work performed on an emergency basis, application for permit shall be made within two working days of commencement of work.
A construction permit is required for installation of or alteration to outdoor stationary cryogenic fluid storage systems where the system capacity exceeds the amounts listed in Table 105.5.11. Maintenance performed in accordance with this code is not considered to be an alteration and does not require a construction permit.
A construction permit is required for installation of or modification to in-building, two-way emergency responder communication coverage systems and related equipment. Maintenance performed in accordance with this code is not considered to be a modification and does not require a construction permit.
A construction permit is required for installation of or modification to fire alarm and detection systems and related equipment. Maintenance performed in accordance with this code is not considered to be a modification and does not require a construction permit.
A construction permit is required:
- To install, repair or modify a pipeline for the transportation of flammable or combustible liquids.
- To install, construct or alter tank vehicles, equipment, tanks, plants, terminals, wells, fuel-dispensing stations, refineries, distilleries and similar facilities where flammable and combustible liquids are produced, processed, transported, stored, dispensed or used.
- To install, alter, remove, abandon or otherwise dispose of a flammable or combustible liquid tank.
A construction permit is required to install stationary fuel cell power systems.
A construction permit is required for the installation of or modification to gas detection systems. Maintenance performed in accordance with this code is not considered a modification and shall not require a permit.
A construction permit is required for the installation of or modification to a gate or barricade across a fire apparatus access road.
A construction permit is required to install, repair damage to, abandon, remove, place temporarily out of service, or close or substantially modify a storage facility or other area regulated by Chapter 50 where the hazardous materials in use or storage exceed the amounts listed in Table 105.5.22.
Exceptions:
- Routine maintenance.
- For repair work performed on an emergency basis, application for permit shall be made within two working days of commencement of work.
A construction permit is required for the installation of or modification to a structure with more than 500 square feet (46 m2), including aisles, of high-piled combustible storage. Maintenance performed in accordance with this code is not considered to be a modification and does not require a construction permit.
A construction permit is required for installation of industrial ovens regulated by Chapter 30.
Exceptions:
- Routine maintenance.
- For repair work performed on an emergency basis, application for permit shall be made within two working days of commencement of work.
Construction permits are required for installation of or alteration to smoke control or smoke exhaust systems. Maintenance performed in accordance with this code is not considered to be an alteration and does not require a permit.
A single construction permit is required to erect and take down a temporary special event structure.
A construction permit is required to install or modify a spray room, dip tank or booth. Maintenance performed in accordance with this code is not considered to be a modification and does not require a permit.
A construction permit is required to erect an air-supported temporary membrane structure, a temporary stage canopy or a tent having an area in excess of 400 square feet (37 m2).
Exceptions:
- Tents used exclusively for recreational camping purposes.
- Funeral tents and curtains, or extensions attached thereto, when used for funeral services.
-
3.1. Individual tents shall have a maximum size of 700 square feet (65 m2).3.2. The aggregate area of multiple tents placed side by side without a fire break clearance of not less than 12 feet (3658 mm) shall not exceed 700 square feet (65 m2) total.3.3. A minimum clearance of 12 feet (3658 mm) to structures and other tents shall be maintained.
Related Code Sections
105.6 Scope and Administration, Required Construction Permits
A construction permit is required for installation of or modification ...
Fire Code 2021 of Colorado > 1 Scope and Administration > 105 Permits > 105.6 Required Construction Permits
105.7 Scope and Administration, Required Construction Permits
A construction permit is required for installation of or modification ...
Fire Code 2018 of Colorado > 1 Scope and Administration > 105 Permits > 105.7 Required Construction Permits
105.6.4 Scope and Administration, Emergency Responder Communication Coverage System
A construction permit is required for installation of or modification to in-building, two-way emergency responder communication coverage systems ...
Fire Code 2021 of Colorado > 1 Scope and Administration > 105 Permits > 105.6 Required Construction Permits > 105.6.4 Emergency Responder Communication Coverage System
105.7.14 Scope and Administration, High-Piled Combustible Storage
A construction permit is required for the installation of or modification to a structure exceeding 500 square feet (46 m2), including aisles ...
Fire Code 2018 of Colorado > 1 Scope and Administration > 105 Permits > 105.7 Required Construction Permits > 105.7.14 High-Piled Combustible Storage
105.6.13 Scope and Administration, High-Piled Combustible Storage
A construction permit is required for the installation of or modification to a structure with more than 500 square feet (46 m2), including aisles ...