(D) Replacements
Go To Full Code Chapter
Replacement of receptacles shall comply with 406.4(D)(1) through (D)(7), as applicable. Arc-fault circuit-interrupter type and ground-fault circuit-interrupter type receptacles shall be installed in a readily accessible location.
(1) Grounding-Type Receptacles
Where a grounding means exists in the receptacle enclosure or an equipment grounding conductor is installed in accordance with 250.130(C), grounding-type receptacles shall be used and shall be connected to the equipment grounding conductor in accordance with 406.4(C) or 250.130(C).
(2) Non—Grounding-Type Receptacles
Where attachment to an equipment grounding conductor does not exist in the receptacle enclosure, the installation shall comply with 406.4(D)(2)(a), (D)(2)(b), or (D)(2)(c).
(a) A non—grounding-type receptacle(s) shall be permitted to be replaced with another non—grounding-type receptacle(s).
(b) A non—grounding-type receptacle(s) shall be permitted to be replaced with a ground-fault circuit interrupter-type of receptacle(s). These receptacles or their cover plates shall be marked "No Equipment Ground." An equipment grounding conductor shall not be connected from the ground-fault circuit-interrupter-type receptacle to any outlet supplied from the ground-fault circuit-interrupter receptacle.
(c) A non-grounding-type receptacle(s) shall be permitted to be replaced with a grounding-type receptacle(s) where supplied through a ground-fault circuit interrupter. Where grounding-type receptacles are supplied through the ground-fault circuit interrupter, grounding-type receptacles or their cover plates shall be marked "GFCI Protected" and "No Equipment Ground," visible after installation. An equipment grounding conductor shall not be connected between the grounding-type receptacles.
Informational Note No. 1: Some equipment or appliance manufacturers require that the branch circuit to the equipment or appliance includes an equipment grounding conductor.
Informational Note No. 2: See 250.114 for a list of a cord-and-plug-connected equipment or appliances that require an equipment grounding conductor.
(3) Ground-Fault Circuit-Interrupter Protection
Ground-fault circuit-interrupter protected receptacles shall be provided where replacements are made at receptacle outlets that are required to be so protected elsewhere in this Code.
Exception: Where the outlet box size will not permit the installation of the GFCI receptacle, the receptacle shall be permitted to be replaced with a new receptacle of the existing type, where GFCI protection is provided and the receptacle is marked "GFCI Protected" and "No Equipment Ground," in accordance with 406.4(D)(2)(a), (D)(2)(b), or (D)(2)(c), as applicable.
(4) Arc-Fault Circuit-Interrupter Protection
If a receptacle outlet located in any areas specified in 210.12(A), (B), or (C) is replaced, a replacement receptacle at this outlet shall be one of the following:
- A listed outlet branch-circuit type arc-fault circuit-interrupter receptacle
- A receptacle protected by a listed outlet branch-circuit type arc-fault circuit-interrupter type receptacle
- A receptacle protected by a listed combination type arc-fault circuit-interrupter type circuit breaker
Exception: Section 210.12(D), Exception, shall not apply to replacement of receptacles.
(5) Tamper-Resistant Receptacles
Listed tamper-resistant receptacles shall be provided where replacements are made at receptacle outlets that are required to be tamper-resistant elsewhere in this Code, except where a non-grounding receptacle is replaced with another non-grounding receptacle.
(6) Weather-Resistant Receptacles
Weather-resistant receptacles shall be provided where replacements are made at receptacle outlets that are required to be so protected elsewhere in this Code.
(7) Controlled Receptacles
Automatically controlled receptacles shall be replaced with equivalently controlled receptacles. If automatic control is no longer required, the receptacle and any associated receptacles marked in accordance with 406.3(E) shall be replaced with a receptacle and faceplate not marked in accordance with 406.3(E).
Upcodes Diagrams
Related Code Sections
1202.2 Historic Buildings, Replacement
Replacement of existing or missing features using original materials shall be permitted. Partial replacement for repairs that match the original ...
1202.2 Historic Buildings, Replacement
Replacement of existing or missing features using original materials shall be permitted. Partial replacement for repairs that match the original ...
(D) Wiring and Protection, Replacement
Where service equipment is replaced, all of the requirements of this section shall apply ...
(D) Equipment for General Use, Replacements
Replacement of receptacles shall comply with 406.4(D)(1) through (D)(7), as applicable. Arc-fault circuit-interrupter type and ground-fault circuit ...
(D) Equipment for General Use, Replacements
Replacement of receptacles shall comply with 406.4(D)(1) through (D)(6), as applicable. Arc-fault circuit-interrupter type and ground-fault circuit ...