Section P3010 Replacement of Underground Building Sewers and Building Drains by Pipe Bursting Methods
JUMP TO FULL CODE CHAPTER
This section shall govern the replacement of existing building sewer and building drain piping by pipe-bursting methods.
The replacement of building sewer and building drain piping by pipe bursting methods shall be limited to gravity drainage piping of sizes 6 inches (150 mm) and smaller. The replacement piping shall be of the same nominal size as the existing piping.
The existing piping sections to be replaced shall be inspected internally by a recorded video camera survey. The survey shall include notations of the position of cleanouts and the depth of connections to the existing piping.
The replacement pipe shall be made of a high-density polyethylene (HDPE) and shall be in compliance with ASTM F714.
Pipe fittings to be connected to the replacement pipe shall be made of high-density polyethylene (HDPE) and shall be in compliance with ASTM D2683.
Where the existing building sewer or building drain did not have cleanouts meeting the requirements of this code, cleanout fittings shall be installed as required by this code.
The completed replacement piping section shall be inspected internally by a recorded video camera survey. The video survey shall be reviewed and approved by the building official prior to pressure testing of the replacement piping system.
The replacement piping system and the connections to the replacement piping shall be tested in accordance with Section P2503.4.
Related Code Sections
Section P3010 Sanitary Drainage, Replacement of Underground Building Sewers and Building Drains by Pipe Bursting Methods
This section shall govern the replacement of existing building sewer and building drain piping by pipe-bursting methods ...
Residential Code 2018 of Kansas > 30 Sanitary Drainage > P3010 Replacement of Underground Building Sewers and Building Drains by Pipe Bursting Methods
Section 716 Sanitary Drainage, Replacement of Underground Building Sewers and Building Drains by Pipe-Bursting Methods
This section shall govern the replacement of existing building sewer and building drain piping by pipe-bursting methods ...
Plumbing Code 2018 of Kansas > 7 Sanitary Drainage > 716 Replacement of Underground Building Sewers and Building Drains by Pipe-Bursting Methods
716.4 Sanitary Drainage, Pipe
The replacement pipe shall be made of high-density polyethylene (HDPE) and shall have a standard dimension ratio (SDR) of 17. The pipe shall ...
Plumbing Code 2018 of Kansas > 7 Sanitary Drainage > 716 Replacement of Underground Building Sewers and Building Drains by Pipe-Bursting Methods > 716.4 Pipe
716.5 Sanitary Drainage, Pipe Fittings
Pipe fittings to be connected to the replacement pipe shall be made of high-density polyethylene (HDPE) and shall be in compliance with ASTM D2683 ...
Plumbing Code 2018 of Kansas > 7 Sanitary Drainage > 716 Replacement of Underground Building Sewers and Building Drains by Pipe-Bursting Methods > 716.5 Pipe Fittings
P3010.5 Sanitary Drainage, Pipe Fittings
Pipe fittings to be connected to the replacement pipe shall be made of high-density polyethylene (HDPE) and shall be in compliance with ASTM D2683 ...
Residential Code 2018 of Kansas > 30 Sanitary Drainage > P3010 Replacement of Underground Building Sewers and Building Drains by Pipe Bursting Methods > P3010.5 Pipe Fittings