7-152 Replacement of an Architect, Engineer, Inspector of Record, Approved Agency, Special Inspector or Contractor
Go To Full Code Chapter
- When replacing any of the listed individuals and/or approved agency the following shall be submitted to the Office:
- Prior to plan approval
- Revised application(s) listing the new responsible individuals) and/or approved agency.
- Following construction document approval
- Revised application(s) listing the new responsible individual(s) and/or approved agency.
- An initial report, prepared by the new responsible individual(s) and/or approved agency, based on field observation(s) that the work performed and materials used and installed to date are in accordance with the project's construction documents. Any observed issues of nonconformance shall be listed in the report. The new individual(s) and/or approved agency shall be responsible for verification of project compliance, pursuant to Section 7-151, for the remainder of the project.
- A final verified report from the individual(s) and/or approved agency being replaced.Exception to (C): In the event that the individual(s) and/or approved agency being replaced refuse to, or cannot provide a final verified report, the owner shall submit a letter to the Office verifying that the work performed and materials used and installed are in accordance with the project's construction documents. The letter shall also list the reason the verified report could not be obtained.
Authority: Health and Safety Code Sections 18929 and 129675—130070.
Reference: Health and Safety Code Section 129850.
Upcodes Diagrams
Related Code Sections
7-152 Safety Standards for Health Facilities, Replacement of an Architect, Engineer, Inspector of Record, Approved Agency, Special Inspector or Contractor
When replacing any of the listed individuals and/or approved agency the following shall be submitted to the Office: Prior to plan approval ...
7-152 Safety Standards for Health Facilities, Replacement of an Architect, Engineer, Inspector of Record, Approved Agency, Special Inspector or Contractor
When replacing any of the listed individuals and/or approved agency the following shall be submitted to the Office: Prior to plan approval ...
4-238 Administrative Regulations for the Division of the State Architect—Structural Safety (DSA-SS), Application for Approval of Project Inspectors, Assistant Inspectors and Special Inspectors
/her qualifications. The architect or registered engineer shall recommend to DSA the approval of the inspector based upon his/her determination ...
4-238 Administrative Regulations for the Division of the State Architect—Structural Safety (DSA-SS), Application for Approval of Project Inspectors, Assistant Inspectors and Special Inspectors
/her qualifications. The architect or registered engineer shall recommend to DSA the approval of the inspector based upon his/her determination ...
4-219 Administrative Regulations for the Division of the State Architect—Structural Safety (DSA-SS), Duties of the Project Inspector
General. The project inspector shall act under the general direction of the architect or registered engineer and under the supervision ...