8.6.2.3 Repair of Speed Governors
Go To Full Code Chapter
Where a repair is made to a speed governor that affects the tripping linkage or speed adjustment mechanism, the governor shall be checked in conformance with 8.6.4.19.2 and 8.6.4.20.2(a).
Where a repair is made to the governor jaws or associated parts that affect the pull-through force, the governor pull-through force shall be checked in conformance with 8.6.4.19.2(b) and 8.6.4.20.2(b). A test tag shall be attached, indicating the date the pull-through test was performed.