// CODE SNIPPET
30.3 Repair Garages for Vehicles Powered by Alternate Fuels
Go To Full Code ChapterSee More
30.3.1 Hydrogen
30.3.1.1
Repair garages servicing self-propelled vehicles
powered by GH2 or LH2 shall comply with NFPA 2.
30.3.1.2 Means of Egress
In a repair garage, the required
number, location, and construction of means of egress shall
meet all applicable requirements for special purpose industrial
occupancies, as set forth in NFPA 101 or as determined in
accordance with the adopted building code. [30A:7.4.2]
30.3.2 LP-Gas-Fueled Vehicles
30.3.2.1 General Construction Requirements
30.3.2.2 Means of Egress
In a repair garage, the required
number, location, and construction of means of egress shall
meet all applicable requirements for special purpose industrial
occupancies, as set forth in NFPA 101, or as determined in
accordance with the adopted building code. [30A:7.4.2]
30.3.2.3 Drainage
In areas of repair garages used for repair
or servicing of vehicles, floor assemblies shall be constructed of
noncombustible materials or, if combustible materials are used
in the assembly, they shall be surfaced with approved, nonabsorbent, noncombustible material, except as indicated in
30.3.2.3.1. [30A:7.4.3]
30.3.2.3.1
Slip-resistant, nonabsorbent, interior floor finishes
having a critical radiant flux not less than 9.87 Btu/in.2-hr
(0.45 W/cm2), as determined by NFPA 253, shall be required.
[30A:7.4.3.1]
30.3.2.3.2
30.3.2.3.3
In areas of repair garages where vehicles are serviced, any floor drains shall be properly trapped and shall
discharge through an oil/water separator to the sewer or to an
outside vented sump. [30A:7.4.3.3]
30.3.2.4 Pits, Belowgrade Work Areas, and Subfloor Work Areas for LP-Gas Powered Vehicles
30.3.2.4.1
Pits, belowgrade work areas, and subfloor work
areas used for lubrication, inspection, and minor automotive
maintenance work shall comply with the provisions of this
chapter, in addition to other applicable requirements of NFPA
30A. [30A:7.4.4.1]
30.3.2.4.2
Walls, floors, and structural supports shall be
constructed of masonry, concrete, steel, or other approved
noncombustible materials. [30A:7.4.4.2]
30.3.2.4.3
In pits, belowgrade work areas, and subfloor work areas, the required number, location, and construction of means of egress shall meet the requirements for special purpose industrial occupancies in Chapter 40 of NFPA 101 or as determined in accordance with the adopted building code. [30A:7.4.4.3]
30.3.2.4.4
Pits, belowgrade work areas, and subfloor work
areas shall be provided with exhaust ventilation at a rate of not
less than 1 ft3/min/ft2 (0.3 m3/min/m2) of floor area at all
times that the building is occupied or when vehicles are parked
in or over these areas. Exhaust air shall be taken from a point
within 12 in. (0.3 m) of the floor. [30A:7.4.4.4]
30.3.2.5 Fixed Fire Protection
Automatic sprinkler protection installed in accordance with the requirements of Section 13.3 shall be provided throughout all buildings containing repair garages, as herein defined, where any one of the following conditions exist:
- The building housing the repair garage is two or more stories, including basements, and the aggregate area of the repair garage exceeds 10,000 ft2 (930 m2).
- The repair garage is one story and exceeds 12,000 ft2 (1115 m2).
- The repair garage is servicing vehicles parked in the basement of the building.
30.3.2.6 Gas Detection System
Repair garages used for repair
of vehicle engine fuel systems fueled by nonodorized gases
shall be provided with an approved flammable gas detection
system. Gas detection systems in repair garages for hydrogen
vehicles shall be in accordance with NFPA 2. [30A:7.4.6]
30.3.2.6.1 System Design
30.3.2.6.1.1
The flammable gas detection system shall be calibrated to the types of fuels or gases used by vehicles to be
repaired. [30A:7.4.6.1.1]
30.3.2.6.1.2
The gas detection system shall be designed to activate when the level of flammable gas exceeds 25 percent of the
lower flammable limit (LFL). [30A:7.4.6.1.2]
30.3.2.6.2 Operation
Activation of the gas detection system shall result in all of the following:
[30A:7.4.6.2]
30.3.2.6.3 Failure of the Gas Detection System
30.3.2.6.4 System Integrity
30.3.2.7 Heating, Ventilating, and Air-Conditioning
30.3.2.7.1
Forced air heating, air-conditioning, and ventilating
systems serving a fuel dispensing area inside a building or a
repair garage shall not be interconnected with any such systems
serving other occupancies in the building. Such systems shall
be installed in accordance with NFPA 90A. [30A:7.5.1]
30.3.2.7.2
Return air openings in areas of repair garages for
vehicles powered by LP-Gas used for the repair or servicing of
vehicles or in a fuel dispensing area shall be not less than 18 in.
(455 mm) above floor level measured to the bottom of the
openings.
30.3.2.7.3
30.3.2.7.4
For repair garages for vehicles powered by LP-Gas,
exhaust duct openings shall be located so that they effectively
remove vapor accumulations at floor level from all parts of the
floor area. Where lighter-than-air gaseous fuel vehicles are
repaired, exhaust duct openings shall be located so that they
effectively remove vapor accumulations at the ceiling level.
30.3.2.8 Heat-Producing Appliances
30.3.2.8.1
30.3.2.8.2 Listing and Restricted Locations
30.3.2.8.2.1
Heat-producing appliances shall be listed for use
in classified areas. [30A:7.6.2.1]
30.3.2.8.2.2
Solid fuel stoves, improvised furnaces, salamanders, and space heaters shall not be permitted in areas of repair
garages used and repairing or servicing of vehicles or in a fuel
dispensing area. [30A:7.6.2.2]
30.3.2.8.2.3
Heat-producing equipment in any lubrication room or service room where there is no dispensing or transferring of Class I or Class II liquids or LP-Gas, when installed in accordance with Chapter 7 of NFPA 30A shall be listed. [30A:7.6.2.3]
30.3.2.8.3
Heat-producing appliances shall be permitted to be
installed in a special room that is separated from areas that are
classified as Division 1 or Division 2, in accordance with Chapter 8 of NFPA 30A, by walls that are constructed to prevent the
transmission of vapors, that have a fire resistance rating of at
least 1 hour, and that have no openings in the walls that lead to
a classified area within 8 ft (2.4 m) of the floor. Specific small
openings through the wall, such as for piping and electrical
conduit, shall be permitted, provided the gaps and voids are
filled with a fire-resistant material to resist transmission of
vapors. All air for combustion purposes shall be taken from
outside the building. This room shall not be used for storage of
combustible materials, except for fuel storage as permitted by
the standards referenced in 30.2.8.9. [30A:7.6.3]
30.3.2.8.4
Heat-producing appliances using gas or oil fuel
shall be permitted to be installed in a lubrication or service
room where there is no dispensing or transferring of Class I
liquids, including the open draining of automotive gasoline
tanks, provided the bottom of the combustion chamber is at
least 18 in. (455 mm) above the floor and the appliances are
protected from physical damage. [30A:7.6.4]
30.3.2.8.5
Heat-producing appliances using gas or oil fuel
listed for use in garages shall be permitted to be installed in
lubrication rooms, service rooms, or fuel dispensing areas
where Class I liquids are dispensed or transferred, provided the
equipment is installed at least 8 ft (2.4 m) above the floor.
[30A:7.6.5]
30.3.2.8.6
Where repairs are conducted on lighter-than-air-fueled vehicles, open flame heaters or heating equipment with exposed surfaces having a temperature in excess of 750°F (399°C) shall not be permitted in areas subject to ignitible concentrations of gas. [30A:7.6.6]
30.3.2.8.7
Electrical heat-producing appliances shall meet the
requirements of Chapter 8 of NFPA 30A. [30A:7.6.7]
30.3.2.8.8
Fuels used shall be of the type and quality specified
by the manufacturer of the heating appliance. Crankcase drainings shall not be used in oil-fired appliances, unless the appliances are specifically approved for such use. [30A:7.6.8]
30.3.2.8.9
Heat-producing appliances shall be installed to
meet the requirements of NFPA 31, NFPA 54, NFPA 82, NFPA
90A, and NFPA 211, as applicable, except as hereinafter specifically provided. [30A:7.6.9]
30.3.3 CNG Fueled Vehicles and LNG Fueled Vehicles
30.3.3.1 Applicability
30.3.3.1.1
Paragraph 30.3.3 shall apply to the construction of
new buildings, existing buildings, and portions of buildings
serving as repair garages and repair areas for CNG and LNG
vehicles. [30A:7.8.1.1]
30.3.3.1.2
30.3.3.2 Occupancy Classification
30.3.3.3 Means of Egress
In a repair garage, the required
number, location, and construction of means of egress shall
meet all applicable requirements for special purpose industrial
occupancies as set forth in NFPA 101 or as determined in
accordance with the adopted building code. [30A:7.8.3]
30.3.3.4 Definition and Classification of Repair Areas Serving CNG and LNG Vehicle Repair
30.3.3.4.1 Applicability
30.3.3.4.2 CNG Repair Area Classification
CNG vehicle repair areas shall be classified according to Table 30.3.3.4.2. [30A:7.8.4.2]
[30A:Table 7.8.4.2]
Type of Repair
|
Minimum Repair Area
Classification |
|
≤500
|
Minor ongoing repair work or unattended vehicle storage while
undergoing minor repair
|
Minor repair area
|
≤500
|
Major ongoing repair work or unattended vehicle storage while
undergoing major repair
|
Major repair area
|
>500
|
Ongoing major or minor repair work or unattended vehicle storage while
undergoing major or minor repair
|
Major repair area
|
30.3.3.4.3 LNG Repair Area Classification
LNG vehicle repair areas shall be classified according to Table 30.3.3.4.3. [30A:7.8.4.3]
*See 30.3.3.4.3.1 and 30.3.3.4.3.2.
[30A:Table 7.8.4.3]
Vehicle Status
|
Type of Vehicle Repair
|
Minimum Repair Area
Classification |
|
<65% of tank
MAWP* |
Any liquid
volume |
Minor ongoing repair work or unattended vehicle
storage while undergoing
minor repair
|
Minor (ongoing repair work) or major repair area
(unattended vehicle storage)
|
Major ongoing repair work or unattended vehicle
storage while undergoing
major repair
|
Major repair |
[30A:Table 7.8.4.3]
30.3.3.4.3.1
All vehicles upon first entering the facility shall have a tank pressure less than 65 percent of the tank maximum allowable working pressure (MAWP) as per the ASME Boiler Pressure Vessel Code. [30A:7.8.4.3.1]
30.3.3.4.3.2
High-pressure fuel systems shall be depressurized
in accordance with the original equipment manufacturers'
recommended maintenance procedures. [30A:7.8.4.3.2]
30.3.3.5 Drainage
In areas of repair garages used for repair
or servicing of vehicles, floor assemblies shall be constructed of
noncombustible materials or combustible materials. [30A:7.8.5]
30.3.3.5.1
If combustible materials are used in the floor assembly, they shall meet the provisions of 30.3.3.5.2. [30A:7.8.5.1]
30.3.3.5.2
Combustible materials used in the floor assembly
shall be surfaced with approved, nonabsorbent, noncombustible material, except as indicated in 30.3.3.5.3. [30A:7.8.5.2]
30.3.3.5.3
Major repair garages and major repair areas serving LNG-fueled vehicles shall comply with the following:
[30A:7.8.5.3]
30.3.3.5.4
Where installed, slip-resistant, nonabsorbent interior floor finishes shall have a critical radiant flux of not less
than 9.87 Btu/in.2-hr (0.45 W/cm2), as determined by NFPA
253. [30A:7.8.5.4]
30.3.3.5.5
30.3.3.5.6
In areas of repair garages where vehicles are serviced, floor drains shall be properly trapped and discharge
through an oil/water separator either to the sewer or to an
outside vented sump. [30A:7.8.5.6]
Related Code Sections
30.3 Motor Fuel Dispensing Facilities and Repair Garages, Repair Garages for Vehicles Powered by Alternate Fuels
of repair garages for
vehicles powered by LP-Gas used for the repair or servicing of
vehicles or in a fuel dispensing area shall be not less than 18 ...
30.3.1.2 Motor Fuel Dispensing Facilities and Repair Garages, Means of Egress
In a repair garage, the required
number, location, and construction of means of egress shall
meet all applicable requirements for special purpose ...
30.3.2.7 Motor Fuel Dispensing Facilities and Repair Garages, Heating, Ventilating, and Air-Conditioning
for
vehicles powered by LP-Gas used for the repair or servicing of
vehicles or in a fuel dispensing area shall be not less than 18 in.
(455 mm) above floor ...
30.3.2.5 Motor Fuel Dispensing Facilities and Repair Garages, Fixed Fire Protection
(1115 m2).
The repair garage is servicing vehicles parked in the basement of the building.
...
30.3.2.1 Motor Fuel Dispensing Facilities and Repair Garages, General Construction Requirements
In repair
garages, where CNG-fueled vehicles, LNG-fueled vehicles, or
LP-Gas-fueled vehicles are repaired, all applicable requirements of NFPA 52 ...