610.1 Renewable Energy Systems Requirements
JUMP TO FULL CODE CHAPTER
Buildings that consume energy shall comply with this section. Each building or surrounding lot or building site where there are multiple buildings on the building site shall be equipped with one or more renewable energy systems in accordance with this section.
Renewable energy systems shall comply with the requirements of Section 610.2 for solar photovoltaic systems, Section 610.3 for wind systems, or Section 610.4 for solar water heating systems, and Section 610.5 for performance monitoring and metering of these systems as approved by the code official. These systems shall be commissioned in accordance with the requirements of Section 611.
Exception: Renewable energy systems are not required for the following:
- Buildings or building sites where there are multiple buildings on the building site providing not less than 2 percent of the total estimated annual energy use of the building, or collective buildings on the site, with onsite renewable energy using a combination of renewable energy generation systems complying with the requirements of Section 610.2, 610.3, or 610.4.
- Where not less than 4 percent of the total annual building energy consumption from renewable generation takes the form of a 10-year commitment to renewable energy credit ownership, confirmed by the code official.
- Where the combined application of onsite generated renewable energy and a commitment to renewable energy credit ownership as confirmed by the code official, totals not less than 4 percent of the total annual building energy consumption from renewable generation.
Buildings and surrounding property or building sites where there are multiple buildings on the building site, that are designed and constructed in accordance with Section 601.3.1, performance-based compliance, shall be equipped with one or more renewable energy systems that have the capacity to provide not less than 2 percent of the total calculated annual energy use of the building, or collective buildings on the site.
Buildings and surrounding property or building sites where there are multiple buildings on the building site, that are designed and constructed in accordance with Section 601.3.2, prescriptive compliance, shall be equipped with one or more renewable energy systems that have the capacity to provide not less than 2 percent of the total estimated annual energy use of the building, or collective buildings on the building site, with onsite renewable energy by calculation demonstrating that onsite renewable energy production has a rating of not less than 1.75 Btu/h (0.5 W) or not less than 0.50 watts per square foot of conditioned floor area, and using any single or combination of renewable energy generation systems meeting the requirements of Sections 610.2, 610.3, or 610.4.
Related Code Sections
610.1 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION, Renewable Energy Systems Requirements
be commissioned in accordance with the requirements of Section 611. Exception: Renewable energy systems are not required for the following: Buildings ...
Green Construction Code 2012 of Maryland > 6 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION > 610 Building Renewable Energy Systems > 610.1 Renewable Energy Systems Requirements
607.4 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION, Snowmelt Systems
renewable energy system. A heat recovery system. Exception: Emergency service ingress and egress are exempt from the requirements of Section ...
Green Construction Code 2012 of Maryland > 6 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION > 607 Building Service Water Heating Systems > 607.4 Snowmelt Systems
R403.10.3 [RE] Residential Energy Efficiency, Covers
or an on-site renewable energy system, covers or other vapor-retardant means shall not be required ...
Energy Conservation Code 2018 of Maryland > 4 [RE] Residential Energy Efficiency > R403 Systems > R403.10 Pools and Permanent Spa Energy Consumption (Mandatory) > R403.10.3 Covers
N1103.10.3 [RE] Energy Efficiency, (R403.10.3) Covers
or an on-site renewable energy system, covers or other vapor-retardant means shall not be required ...
Residential Code 2018 of Maryland > 11 [RE] Energy Efficiency > N1103 (R403) Systems > N1103.10 (R403.10) Pools and Permanent Spa Energy Consumption (Mandatory) > N1103.10.3 (R403.10.3) Covers
C404.9.3 [CE] Commercial Energy Efficiency, Covers
energy such as from a heat pump or on-site renewable energy system, covers or other vapor-retardant means shall not be required ...
Energy Conservation Code 2018 of Maryland > 4 [CE] Commercial Energy Efficiency > C404 Service Water Heating (Mandatory) > C404.9 Energy Consumption of Pools and Permanent Spas (Mandatory) > C404.9.3 Covers