603.3.7 Renewable and Waste Energy
JUMP TO FULL CODE CHAPTER
Equipment and systems providing electric power through conversion of solar energy directly to electric power shall be capable of being metered so that the peak electric power (kW) provided to the building and its systems or to off-site entities can be determined at 15-minute intervals and the amount of electric power (kWh) provided to the building and its systems can be determined at intervals of 1 hour or less.
Equipment and systems providing heat to fluids or gases through the capture of solar energy shall be capable of being metered so that the peak thermal energy (Btu/h) provided to the building and its systems or to off-site entities can be determined at 15-minute intervals and the amount of heat captured (Btu) for delivery to the building and its systems can be determined intervals of 1 hour or less.
Exception: Systems with a rated output of less than 100 kBtu/hr shall not be required to have the capacity to be metered.
Equipment and systems providing energy through the capture of waste heat shall be capable of being metered so that the amount of heat captured and delivered to the building and its systems can be determined at intervals of 1 hour or less.
Exception: Systems with a rated output of less than 100 kBtu/hr shall not be required to have the capacity to be metered.
Equipment and systems providing electric power through conversion of wind energy directly to electric power shall be capable of being metered so that the peak electric power (kW) provided to the building and its systems or to off-site entities can be determined at 15-minute intervals and the amount of electric power (kWh) provided to the building and its systems can be determined at intervals of 1 hour or less.
Equipment and systems providing electric power through conversion of other forms of renewable energy directly to electric power shall be capable of being metered so that the peak electric power (kW) provided to the building and its systems or to off-site entities can be determined at 15-minute intervals and the amount of electric power (kWh) provided to the building and its systems can be determined at intervals of 1 hour or less.
Related Code Sections
603.3.7 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION, Renewable and Waste Energy
Equipment and systems providing energy from renewable or waste energy sources which is included in the determination of the building zEPI, shall ...
Green Construction Code 2012 > 6 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION > 603 Energy Metering, Monitoring and Reporting > 603.3 Energy-Type Metering > 603.3.7 Renewable and Waste Energy
603.3.7 Energy Conservation, Efficiency and Co2e Emission Reduction, Renewable and Waste Energy
Equipment and systems providing energy from renewable or waste energy sources which is included in the determination of the building zEPI, shall ...
Green Construction Code 2015 > 6 Energy Conservation, Efficiency and Co2e Emission Reduction > 603 Energy Metering, Monitoring and Reporting > 603.3 Energy-Type Metering > 603.3.7 Renewable and Waste Energy
601.5.1 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION, Multiple Buildings on a Site
is derived from either renewable or waste energy, or both sources located on the building site, within individual buildings, or on individual buildings ...
Green Construction Code 2012 > 6 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION > 601 General > 601.5 Multiple Buildings on a Site and Mixed Use Buildings > 601.5.1 Multiple Buildings on a Site
603.3.7.1 Energy Conservation, Efficiency and Co2e Emission Reduction, Solar Electric
Equipment and systems providing electric power through conversion of solar energy directly to electric power shall be capable of being metered so ...
Green Construction Code 2015 > 6 Energy Conservation, Efficiency and Co2e Emission Reduction > 603 Energy Metering, Monitoring and Reporting > 603.3 Energy-Type Metering > 603.3.7 Renewable and Waste Energy > 603.3.7.1 Solar Electric
603.3.7.2 Energy Conservation, Efficiency and Co2e Emission Reduction, Solar Thermal
Equipment and systems providing heat to fluids or gases through the capture of solar energy shall be capable of being metered so that the peak ...
Green Construction Code 2015 > 6 Energy Conservation, Efficiency and Co2e Emission Reduction > 603 Energy Metering, Monitoring and Reporting > 603.3 Energy-Type Metering > 603.3.7 Renewable and Waste Energy > 603.3.7.2 Solar Thermal