2306.7.7 Remote Pumping Systems
Go To Full Code Chapter
2306.7.7.1 Leak Detection
Where remote pumps are used to supply fuel dispensers, each pump shall have installed on the discharge side a listed leak detection device that will detect a leak in the piping and dispensers and provide an indication. A leak detection device is not required if the piping from the pump discharge to under the dispenser is above ground and visible.
2306.7.7.2 Location
Remote pumps installed above grade, outside of buildings, shall be located not less than 10 feet (3048 mm) from lines of adjoining property that can be built on and not less than 5 feet (1524 mm) from any building opening. Where an outside pump location is impractical, pumps are permitted to be installed inside buildings as provided for dispensers in Section 2301.4 and Chapter 57. Pumps shall be substantially anchored and protected against physical damage.
Upcodes Diagrams
Related Code Sections
2306.7.7 Motor Fuel-Dispensing Facilities and Repair Garages, Remote Pumping Systems
Remote pumping systems for liquid fuels shall comply with Sections 2306.7.7.1 and 2306.7.7.2 ...
2306.7.7 Motor Fuel-Dispensing Facilities and Repair Garages, Remote Pumping Systems
Remote pumping systems for liquid fuels shall comply with Sections 2306.7.7.1 and 2306.7.7.2 ...
2907.2 Manufacture of Organic Coatings, Valves
Valves shall be of an indicating type. Terminal valves on remote pumping systems shall be of the dead-man type, shutting off both the pump ...
2907.2 Manufacture of Organic Coatings, Valves
Valves shall be of an indicating type. Terminal valves on remote pumping systems shall be of the dead-man type, shutting off both the pump ...
Section 2907 Manufacture of Organic Coatings, Process Piping
Valves shall be of an indicating type. Terminal valves on remote pumping systems shall be of the dead-man type ...