605.9 Remote Controls
JUMP TO FULL CODE CHAPTER
Where flammable refrigerants are used and compliance with Section 1106 of the International Mechanical Code is required, remote control of the mechanical equipment and appliances located in the machinery room as required by Sections 605.9.1 and 605.9.2 shall be provided at an approved location immediately outside the machinery room and adjacent to its principal entrance.
A clearly identified switch of the break-glass type or with an approved tamper-resistant cover shall provide off-only control of refrigerant compressors, refrigerant pumps and normally closed automatic refrigerant valves located in the machinery room. Additionally, this equipment shall be automatically shut off when the refrigerant vapor concentration in the machinery room exceeds the vapor detector's upper detection limit or 25 percent of the LEL, whichever is lower.
A clearly identified switch of the break-glass type or with an approved tamper-resistant cover shall provide on-only control of the machinery room ventilation fans.
Related Code Sections
1106.5 Refrigeration, Remote Controls
Remote control of the mechanical equipment and appliances located in the machinery room shall comply with Sections 1106.5.1 and 1106.5.2 ...
Mechanical Code 2021 of Colorado > 11 Refrigeration > 1106 Machinery Room, Special Requirements > 1106.5 Remote Controls
1106.5 Refrigeration, Remote Controls
Remote control of the mechanical equipment and appliances located in the machinery room shall comply with Sections 1106.5.1 and 1106.5.2 ...
Mechanical Code 2015 of Colorado > 11 Refrigeration > 1106 Machinery Room, Special Requirements > 1106.5 Remote Controls
1106.6 Refrigeration, Remote Controls
Remote control of the mechanical equipment and appliances located in the machinery room shall comply with Sections 1106.6.1 and 1106.6.2 ...
Mechanical Code 2018 of Colorado > 11 Refrigeration > 1106 Machinery Room, Special Requirements > 1106.6 Remote Controls
(C) Wiring and Protection, Remote Control
building or structure. In such cases, the service disconnecting means shall be permitted to be electrically operated by a readily accessible, remote ...
National Electrical Code 2020 of Colorado > 2 Wiring and Protection > 230 Services > 230.205 Disconnecting Means > (C) Remote Control
(B) Special Occupancies, Remotely Controlled
Devices are operated electrically from a pilot-type control console or panel. Pilot control panels either shall be part of the switchboard or shall ...
National Electrical Code 2020 of Colorado > 5 Special Occupancies > 520 Theaters, Audience Areas of Motion Picture and Television Studios, Performance Areas, and Similar Locations > 520.26 Type of Switchboard > (B) Remotely Controlled