// CODE SNIPPET
603.5 Relocatable Power Taps and Current Taps
Go To Full Code Chapter
The construction and use of current taps and relocatable taps shall be in accordance with NFPA 70 and this code.
603.5.1 Listing
Relocatable power taps shall be listed in accordance with UL 1363. Current taps shall be listed and labeled in accordance with UL 498A.
603.5.1.1 Listing in Group I-2 Occupancies and Ambulatory Care Facilities
In Group I-2 occupancies and ambulatory care facilities, relocatable power taps shall be listed in accordance with UL 1363 except under the following conditions:
- In Group I-2, Condition 2 occupancies, relocatable power taps providing power to patient care-related electrical equipment in the patient care vicinity, as defined by NFPA 99, shall be listed in accordance with UL 1363A or UL 60601-1.
- In Group I-2, Condition 1 facilities, in care recipient rooms using line-operated patient care-related electrical equipment, relocatable power taps in the patient care vicinity, as defined by NFPA 99, shall be listed in accordance with UL 1363A or UL 60601-1.
- In ambulatory care facilities, relocatable power taps providing power to patient care-related electrical equipment in the patient care vicinity, as defined by NFPA 99, shall be listed in accordance with UL 1363A or UL 60601-1.
603.5.2 Application and Use
Relocatable power taps and current taps shall be directly connected to a permanently installed receptacle.
Exceptions:
- Where approved for use in a Group A occupancy or in a meeting room in a Group B occupancy, not more than five relocatable power taps shall be permitted to be connected together or connected to an extension cord for temporary use to supply power to electronic equipment.
- Current taps and relocatable power taps shall not be required to connect directly to a permanently installed receptacle outlet where used for 90 days or less for the purpose of testing the performance of such devices.
603.5.3 Installation
Relocatable power tap cords shall not extend through walls, ceilings, floors, under doors or floor coverings, or be subject to environmental or physical damage.
Related Code Sections
603.5 Building Services and Systems, Relocatable Power Taps and Current Taps
Relocatable power taps shall be listed in accordance with UL 1363. Current taps shall ...
603.6 Building Services and Systems, Extension Cords
into an approved receptacle, relocatable power tap or current tap and, except for approved multiplug extension cords, shall serve only one portable ...
Section 603 Building Services and Systems, Electrical Equipment, Wiring and Hazards
to an extension cord for temporary use to supply power to electronic equipment. Current taps and relocatable power taps shall not be required to connect ...
(2) Special Conditions, Taps
Where power source output connections are made at feeders, all taps shall be sized based on the sum of 125 percent of all power source(s) output ...
604.4.1 Building Services and Systems, Power Tap Design
Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL ...