1807.2.4 Reinforced Masonry Retaining Walls
Go To Full Code Chapter
Vertical reinforcement for masonry retaining walls shall comply with Table 1807.2.4 or shall be designed in accordance with TMS 402/ACI 530/ASCE 5. Masonry shall be fully grouted with a minimum f'm of 1,500 psi (10 343 kPa). Mortar for masonry shall be Type M or S and laid in running bond. The specified location of the reinforcement shall equal or exceed the effective depth distance, d, noted in Table 1807.2.4 and shall be measured from the exposed side of the wall to the center of the vertical reinforcement. Footings for reinforced masonry retaining walls shall be designed in accordance with ACI 318.
Nominal Wall thickness [(in.) (mm)] | Wall depth, H, ft. (m) | Reinforcement size & spacing for equivalent fluid weight of soil, pcf (kN/m3), of: | ||
30 (4.7) | 45 (7.1) | 60 (9.4) | ||
8 (203) | 4.0 (1.2) | #4 at 64 in. | #4 at 40 in. | #4 at 32 in. |
4.7 (1.4) | #4 at 40 in. | #4 at 24 in. | #4 at 16 in. | |
5.3 (1.6) | #4 at 24 in. | #4 at 16 in. | #5 at 16 in. | |
6.0 (1.8) | #5 at 24 in. | #6 at 16 in. | #8 at 16 in. | |
6.7 (2.0) | #5 at 16 in. | #6 at 8 in. | — | |
10 (254) | 4.0 (1.2) | #4 at 72 in. | #4 at 64 in. | #4 at 48 in. |
4.7 (1.4) | #4 at 56 in. | #4 at 40 in. | #4 at 24 in. | |
5.3 (1.6) | #4 at 40 in. | #4 at 24 in. | #4 at 16 in. | |
6.0 (1.8) | #4 at 24 in. | #4 at 16 in. | #5 at 16 in. | |
6.7 (2.0) | #4 at 16 in. | #5 at 16 in. | #6 at 16 in. | |
7.3 (2.2) | #5 at 24 in. | #6 at 16 in. | #6 at 8 in. | |
8.0 (2.4) | #5 at 16 in. | #6 at 8 in. | — | |
12 (305) | 4.0 (1.2) | #4 at 72 in. | #4 at 72 in. | #4 at 64 in. |
4.7 (1.4) | #4 at 72 in. | #4 at 48 in. | #4 at 40 in. | |
5.3 (1.6) | #4 at 48 in. | #4 at 32 in. | #4 at 24 in. | |
6.0 (1.8) | #4 at 32 in. | #4 at 24 in. | #4 at 16 in. | |
6.7 (2.0) | #4 at 24 in. | #4 at 16 in. | #5 at 16 in. | |
7.3 (2.2) | #4 at 16 in. | #5 at 16 in. | #6 at 16 in. | |
8.0 (2.4) | #5 at 24 in. | #5 at 16 in. | #7 at 16 in. | |
8.7 (2.7) | #5 at 16 in. | #7 at 16 in. | #7 at 8 in. | |
9.3 (2.8) | #6 at 16 in. | #7 at 8 in. | — |
Related Code Sections
1807.2.4 Soils and Foundations, Reinforced Masonry Retaining Walls
Vertical reinforcement for masonry retaining walls shall comply with Table 1807.2.4 or shall be designed in accordance with TMS 402/ACI 530/ASCE 5 ...
R404.1.2.2.1 Foundations, Concrete Foundation Stem Walls Supporting Above-Grade Concrete Walls
-on-ground shall comply with this section. Where unbalanced backfill retained by the stem wall is less than or equal to 18 inches (457 mm), the stem wall ...
2014 FBC - Residential, 5th edition > 4 Foundations > R404 Foundation and Retaining Walls > R404.1 Concrete and Masonry Foundation Walls > R404.1.2 Concrete Foundation Walls > R404.1.2.2 Reinforcement for Foundation Walls > R404.1.2.2.1 Concrete Foundation Stem Walls Supporting Above-Grade Concrete Walls
R404.1.3.2.1 Foundations, Concrete Foundation Stem Walls Supporting Above-Grade Concrete Walls
shall comply with this section. Where unbalanced backfill retained by the stem wall is less than or equal to 18 inches (457 mm), the stem wall ...
2020 FBC - Residential, 7th edition > 4 Foundations > R404 Foundation and Retaining Walls > R404.1 Concrete and Masonry Foundation Walls > R404.1.3 Concrete Foundation Walls > R404.1.3.2 Reinforcement for Foundation Walls > R404.1.3.2.1 Concrete Foundation Stem Walls Supporting Above-Grade Concrete Walls
R404.1.3.2.1 Foundations, Concrete Foundation Stem Walls Supporting Above-Grade Concrete Walls
shall comply with this section. Where unbalanced backfill retained by the stem wall is less than or equal to 18 inches (457 mm), the stem wall ...
2017 FBC - Residential, 6th edition > 4 Foundations > R404 Foundation and Retaining Walls > R404.1 Concrete and Masonry Foundation Walls > R404.1.3 Concrete Foundation Walls > R404.1.3.2 Reinforcement for Foundation Walls > R404.1.3.2.1 Concrete Foundation Stem Walls Supporting Above-Grade Concrete Walls
R404.1.3.3.7.1 Foundations, Steel Reinforcement
Steel reinforcement shall comply with the requirements of ASTM A615, A706, or A996. ASTM A996 bars produced from rail steel shall be Type R. In ...