R609.3 Reinforced Grouted Multiple-Wythe Masonry
JUMP TO FULL CODE CHAPTER
The thickness of grout or mortar between masonry units and reinforcement shall not be less than 1/4 inch (7 mm), except that 1/4-inch (7 mm) bars may be laid in horizontal mortar joints at least 1/2 inch (13 mm) thick, and steel wire reinforcement may be laid in horizontal mortar joints at least twice the thickness of the wire diameter.
Related Code Sections
R609.3 Wall Construction, Reinforced Grouted Multiple-Wythe Masonry
Reinforced grouted multiple-wythe masonry shall conform to all the requirements specified in Sections R609.1 and R609.2 and the requirements ...
Minnesota Residential Code 2015 > 6 Wall Construction > R609 Grouted Masonry > R609.3 Reinforced Grouted Multiple-Wythe Masonry
R606.3 Wall Construction, Construction Requirements
Grouted multiple-wythe masonry shall conform to all the requirements specified in Section R606.3.5 and the requirements ...
2020 Minnesota Residential Code > 6 Wall Construction > R606 General Masonry Construction > R606.3 Construction Requirements
R609.2 Wall Construction, Grouted Multiple-Wythe Masonry
Grouted multiple-wythe masonry shall conform to all the requirements specified in Section R609.1 and the requirements of this section ...
Minnesota Residential Code 2015 > 6 Wall Construction > R609 Grouted Masonry > R609.2 Grouted Multiple-Wythe Masonry
Section R608 Wall Construction, Multiple-Wythe Masonry
The facing and backing of multiple-wythe masonry walls shall be bonded in accordance with Section R608.1.1, R608.1.2 or R608.1.3. In cavity walls ...
R609.2.2 Wall Construction, Grout Spaces
Fine grout shall be used when interior vertical space to receive grout does not exceed 2 inches (51 mm) in thickness. Interior vertical spaces ...
Minnesota Residential Code 2015 > 6 Wall Construction > R609 Grouted Masonry > R609.2 Grouted Multiple-Wythe Masonry > R609.2.2 Grout Spaces