1006.2.2.2 Refrigeration Machinery Rooms
Go To Full Code Chapter
Machinery rooms larger than 1,000 square feet (93 m2) shall have not less than two exits or exit access doorways. Where two exit access doorways are required, one such doorway is permitted to be served by a fixed ladder or an alternating tread device. Exit access doorways shall be separated by a horizontal distance equal to one-half the maximum horizontal dimension of the room.
All portions of machinery rooms shall be within 150 feet (45 720 mm) of an exit or exit access doorway. An increase in exit access travel distance is permitted in accordance with Section 1017.1.
Exit and exit access doorways shall swing in the direction of egress travel and shall be equipped with panic hardware, regardless of the occupant load served. Exit and exit access doorways shall be tight fitting and self-closing.
Upcodes Diagrams
Related Code Sections
1006.2.2.2 Means of Egress, Refrigeration Machinery Rooms
Machinery rooms larger than 1,000 square feet (93 m2) shall have not less than two exits or exit access doorways. Where two exit access doorways ...
1006.2.2.2 Means of Egress, Refrigeration Machinery Rooms
Machinery rooms larger than 1,000 square feet (93 m2) shall have not less than two exits or exit access doorways. Where two exit access doorways ...
1010.2.9.1 Means of Egress, Refrigeration Machinery Room
Refrigeration machinery rooms larger than 1,000 square feet (93 m2) shall have not less than two exit or exit access doorways that swing ...
1106.4.1 Refrigeration, Ventilation System Activation
Ventilation shall be activated by the refrigerant detection system in the machinery room. Refrigerant detection systems shall ...
1105.3 Refrigeration, Refrigerant Detector
Refrigerant detectors in machinery rooms shall be provided as required by Sections 608.9 and 608.18 of the International Fire Code ...