C403.2.17 Refrigerated Display Cases
JUMP TO FULL CODE CHAPTER
Site-assembled or site-constructed refrigerated display cases shall comply with the following:
- Lighting and glass doors in refrigerated display cases shall be controlled by one of the following:
- 1.1. Time switch controls to turn off lights during nonbusiness hours. Timed overrides for display cases shall turn the lights on for up to 1 hour and shall automatically time out to turn the lights off.
- 1.2. Motion sensor controls on each display case section that reduce lighting power by at least 50 percent within 3 minutes after the area within the sensor range is vacated.
- Low-temperature display cases shall incorporate temperature-based defrost termination control with a time-limit default. The defrost cycle shall terminate first on an upper temperature limit breach and second upon a time limit breach.
- Antisweat heater controls shall reduce the energy use of the antisweat heater as a function of the relative humidity in the air outside the door or to the condensation on the inner glass pane.
Related Code Sections
C403.2.17 [CE] Commercial Energy Efficiency, Refrigerated Display Cases
Site-assembled or site-constructed refrigerated display cases shall comply with the following: Lighting and glass doors in refrigerated display ...
Energy Conservation Code 2015 of Colorado > 4 [CE] Commercial Energy Efficiency > C403 Building Mechanical Systems > C403.2 Provisions Applicable to All Mechanical Systems (Mandatory) > C403.2.17 Refrigerated Display Cases
C403.10.3 [CE] Commercial Energy Efficiency, Refrigerated Display Cases (Mandatory)
Site-assembled or site-constructed refrigerated display cases shall comply with the following: Lighting and glass doors in refrigerated display ...
Energy Conservation Code 2018 of Colorado > 4 [CE] Commercial Energy Efficiency > C403 Building Mechanical Systems > C403.10 Refrigeration Equipment Performance > C403.10.3 Refrigerated Display Cases (Mandatory)
709.4.1 Sanitary Drainage, Clear-Water Waste Receptors
Where waste receptors such as floor drains, floor sinks and hub drains receive only clear-water waste from display cases, refrigerated display cases ...
Plumbing Code 2018 of Colorado > 7 Sanitary Drainage > 709 Fixture Units > 709.4 Values for Indirect Waste Receptor > 709.4.1 Clear-Water Waste Receptors
413.2 Fixtures, Faucets and Fixture Fittings, Floor Drains
be provided to the drain inlet. Ready access shall be provided to floor drains. Exception: Floor drains serving refrigerated display cases shall ...
Plumbing Code 2018 of Colorado > 4 Fixtures, Faucets and Fixture Fittings > 413 Floor and Trench Drains > 413.2 Floor Drains
C403.11.3 [CE] Commercial Energy Efficiency, Refrigeration Systems
Refrigerated display cases, walk-in coolers or walk-in freezers that are served by remote compressors and remote condensers not located ...
Energy Conservation Code 2021 of Colorado > 4 [CE] Commercial Energy Efficiency > C403 Building Mechanical Systems > C403.11 Refrigeration Equipment Performance > C403.11.3 Refrigeration Systems