605.8.1 Refrigerants Other Than Ammonia
JUMP TO FULL CODE CHAPTER
A detector, or a sampling tube that draws air to a detector, shall be provided at an approved location where refrigerant from a leak is expected to accumulate. The system shall be designed to initiate audible and visible alarms inside of and outside each entrance to the refrigerating machinery room and transmit a signal to an approved location where the concentration of refrigerant detected exceeds the lesser of the following:
- The corresponding TLV-TWA values shown in the California Mechanical Code for the refrigerant classification.
- Twenty-five percent of the lower flammable limit (LFL).
Detection of a refrigerant concentration exceeding the upper detection limit or 25 percent of the lower flammable limit (LFL), whichever is lower, shall stop refrigerant equipment in the machinery room in accordance with Section 605.9.1.
Related Code Sections
606.8.1 Building Services and Systems, Refrigerants Other Than Ammonia
A detector, or
a sampling tube that draws air to a detector, shall be provided
at an approved location where refrigerant from a
leak is expected ...
California Fire Code 2016 > 6 Building Services and Systems > 606 Mechanical Refrigeration > 606.8 Refrigerant Detector > 606.8.1 Refrigerants Other Than Ammonia
605.1.1 Building Services and Systems, Refrigerants Other Than Ammonia
Where a refrigerant other than ammonia is used, refrigeration systems and the buildings in which such systems are installed shall be in accordance ...
California Fire Code 2019 > 6 Building Services and Systems > 605 Mechanical Refrigeration > 605.1 Scope > 605.1.1 Refrigerants Other Than Ammonia
1102.1 Refrigeration, General
Refrigeration systems using a refrigerant
other than ammonia shall comply with this chapter and
ASHRAE 15 ...
606.8 Building Services and Systems, Refrigerant Detector
, detection
shall comply with IIAR 2. For refrigerants other than ammonia,
refrigerant detection shall comply with Section 606.8.1 ...
California Fire Code 2016 > 6 Building Services and Systems > 606 Mechanical Refrigeration > 606.8 Refrigerant Detector
1104.5 Refrigeration, Flammable Refrigerants
The total of Group A2, B2,
A3, and B3 refrigerants, other than R-717 (ammonia), shall
not exceed 1100 pounds (498.9 kg) without approval ...
California Mechanical Code 2016 > 11 Refrigeration > 1104.0 Requirements for Refrigerant and Refrigeration System Use > 1104.5 Flammable Refrigerants