1504.9 Reflectance

NYC Building Code 2014 > 15 Roof Assemblies and Rooftop Structures > 1504 Performance Requirements > 1504.9 Reflectance
JUMP TO FULL CODE CHAPTER
Roof coverings on roofs or setbacks with slope equal to or less than two units vertical in 12 units horizontal (17 percent) shall have:

1. A minimum initial solar reflectance of 0.7 in accordance with ASTM C 1549 or ASTM E 1918, and a minimum thermal emittance of 0.75 as determined in accordance with ASTM C 1371 or ASTM E 408; or

2. A minimum SRI of 78 as determined in accordance with ASTM E 1980.

Exceptions:

1. Terraces on setbacks comprising less than 25 percent of the area of the largest floor plate in the building.

2. Any portion of a roof covered by a green roof system, including such a system with agricultural plantings, in compliance with Section 1507.16.

3. Any portion of a roof used as outdoor recreation space by the occupants of the building that is landscaped, covered by wood decking or covered with a walking surface or other protective surface, provided that such walking surface or protective surface has a minimum initial solar reflectance of 0.3 as determined in accordance with ASTM C 1549 or ASTM E 1918.

4. Ballasted roofs, provided that the ballast has a minimum initial solar reflectance of 0.2 as determined in accordance with ASTM C 1549 or ASTM E 1918.

5. Any portion of a roof that is under mechanical equipment, flush mounted solar panels lying directly on the roof surface, duckboarding, decking, platform, roof tank, cooling tower or any other rooftop structure or equipment exempted by rule by the commissioner.

6. Any roof or portion of a roof composed of glass, metal, clay or concrete tile or plastic/rubber intended to simulate clay or concrete tile, wood, or slate.

7. Any portion of a roof used by a school or daycare center as a playground for children.

8. Any roof, if the amount of rooftop space not subject to exceptions 1 through 7 is in the aggregate less than 100 square feet (9.3 m2).
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


1504.8 Roof Assemblies and Rooftop Structures, Reflectance
a minimum initial solar reflectance of 0.7 in accordance with ASTM C1549 or ASTM E 1918, and a minimum thermal emittance of 0.75 as determined in accordance ...
NYC Building Code 2008 > 15 Roof Assemblies and Rooftop Structures > 1504 Performance Requirements > 1504.8 Reflectance
1504.9 Roof Assemblies and Rooftop Structures, Reflectance
minimum initial solar reflectance of 0.7 in accordance with ASTM C 1549 or ASTM E 1918, and a minimum thermal emittance of 0.75 as determined ...
NYC Building Code 2014 > 15 Roof Assemblies and Rooftop Structures > 1504 Performance Requirements > 1504.9 Reflectance
Section 2613 Plastic, Reflective Plastic Core Insulation
Packages and containers of reflective plastic core insulation delivered to the job site shall show the manufacturer's or supplier's name, product ...
NYC Building Code 2014 > 26 Plastic > 2613 Reflective Plastic Core Insulation
2613.3.1 Plastic, Mounting of Test Specimen
The test specimen shall be mounted on 2-inch-high (51 mm) metal frames so as to create an air space between the unexposed face of the reflective ...
NYC Building Code 2014 > 26 Plastic > 2613 Reflective Plastic Core Insulation > 2613.3 Surface-Burning Characteristics > 2613.3.1 Mounting of Test Specimen
719.2.1 Fire and Smoke Protection Features, Facings
do not apply to facings, coverings, and layers of reflective foil insulation that are installed behind and in substantial contact with the unexposed ...
NYC Building Code 2014 > 7 Fire and Smoke Protection Features > 719 Thermal- And Sound-Insulating Materials > 719.2 Concealed Installation > 719.2.1 Facings
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US