1910.106(i) Refineries, Chemical Plants, and Distilleries
JUMP TO FULL CODE CHAPTER
flammable liquids shall be stored in tanks, in containers, or in portable tanks. Tanks shall be installed in accordance with paragraph (b) of this section. Tanks for the storage of flammable liquids in tank farms and in locations other than process areas shall be located in accordance with paragraph (b)(2)(i) and (ii) of this section.
Wharves handling flammable liquids shall be in accordance with paragraph (f)(4) of this section.
Fired pressure vessels shall be constructed in accordance with the Code for Fired Pressure Vessels, Section I of the ASME Boiler and Pressure Vessel Code - 1968.
Unfired vessels shall be constructed in accordance with the Code for Unfired Pressure Vessels, Section VIII of the ASME Boiler and Pressure Vessel Code - 1968.
Process units shall be located so that they are accessible from at least one side for the purpose of fire control.
Portable fire extinguishment and control equipment shall be provided in such quantities and types as are needed for the special hazards of operation and storage.
Special extinguishing equipment such as that utilizing foam, inert gas, or dry chemical shall be provided as the need is indicated by the special hazards of operation and storage.
Water shall be available in volume and at adequate pressure to supply water hose streams, foam producing equipment, automatic sprinklers, or water spray systems as the need is indicated by the special hazards of operation and storage.
Related Code Sections
1910.106(i) Hazardous Materials, Refineries, Chemical Plants, and Distilleries
Special extinguishing equipment such as that utilizing foam, inert gas, or dry chemical shall be provided as the need ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(i) Refineries, Chemical Plants, and Distilleries
1910.106(i)(5)(iii) Hazardous Materials, Special Equipment
Special extinguishing equipment such as that utilizing foam, inert gas, or dry chemical shall be provided as the need is indicated by the special ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(i) Refineries, Chemical Plants, and Distilleries > 1910.106(i)(5) Fire Control > 1910.106(i)(5)(iii) Special Equipment
1910.106(i)(5)(i) Hazardous Materials, Portable Equipment
Portable fire extinguishment and control equipment shall be provided in such quantities and types as are needed for the special hazards of operation ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(i) Refineries, Chemical Plants, and Distilleries > 1910.106(i)(5) Fire Control > 1910.106(i)(5)(i) Portable Equipment
1910.106(i)(5)(ii) Hazardous Materials, Water Supply
Water shall be available in volume and at adequate pressure to supply water hose streams, foam producing equipment, automatic sprinklers, or water ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(i) Refineries, Chemical Plants, and Distilleries > 1910.106(i)(5) Fire Control > 1910.106(i)(5)(ii) Water Supply
1910.106(i)(3)(i) Hazardous Materials, Fired Vessels
Fired pressure vessels shall be constructed in accordance with the Code for Fired Pressure Vessels, Section I of the ASME Boiler and Pressure Vessel ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(i) Refineries, Chemical Plants, and Distilleries > 1910.106(i)(3) Fired and Unfired Pressure Vessels > 1910.106(i)(3)(i) Fired Vessels