§27-869.03 Reduction in Flue Size
JUMP TO FULL CODE CHAPTER
Conversion from one fuel to another or the use of an existing chimney to service a fireplace or wood burning appliance may require a flue size change for proper operation. This may be done if the redesigned flue meets the criteria for the fuel and chimney type to be used as set forth in this subchapter.
(a) Individual fireclay flue linings, in conformance with reference standard RS 15-14 or the equivalent not less than five-eighths inch thick, may be used but shall be carefully bedded one on the other in medium-duty fireclay refractory mortar in conformance with reference standard RS 15-6 or the equivalent as determined by the commissioner, with close fitting joints left smooth on the inside. Linings shall be separate from the chimney wall and the space between the liner and masonry shall not be filled; only enough mortar shall be used to make a good joint and hold the liners in position.
(b) Cast in place chimney linings.
(1) Cast in place linings shall be installed in accordance with reference standard RS 15-16 and with their listing and acceptance.
(2) The applicant prior to the installation of the lining shall verify that the chimney meets the requirements of reference standard RS 15-4 and is in a sound and uncracked condition, that spalling has been removed and that there are no carbon or creosote deposits.
(a) Individual fireclay flue linings, in conformance with reference standard RS 15-14 or the equivalent not less than five-eighths inch thick, may be used but shall be carefully bedded one on the other in medium-duty fireclay refractory mortar in conformance with reference standard RS 15-6 or the equivalent as determined by the commissioner, with close fitting joints left smooth on the inside. Linings shall be separate from the chimney wall and the space between the liner and masonry shall not be filled; only enough mortar shall be used to make a good joint and hold the liners in position.
(b) Cast in place chimney linings.
(1) Cast in place linings shall be installed in accordance with reference standard RS 15-16 and with their listing and acceptance.
(2) The applicant prior to the installation of the lining shall verify that the chimney meets the requirements of reference standard RS 15-4 and is in a sound and uncracked condition, that spalling has been removed and that there are no carbon or creosote deposits.
Related Code Sections
Section 808 Chimneys and Vents, Reduction of Flue Size
Conversion from one fuel to another or the use of an existing chimney to service a fireplace or wood-burning appliance may require a flue size change ...
Section 808 Chimneys and Vents, Reduction of Flue Size
Conversion from one fuel to another or the use of an existing chimney to service a fireplace or wood-burning appliance may require a flue size change ...
§27-869.03 Chimneys and Gas Vents, Reduction in Flue Size
Conversion from one fuel to another or the use of an existing chimney to service a fireplace or wood burning appliance may require a flue size change ...
NYC 1968 Code (Vol I) > 15 Chimneys and Gas Vents > 2 Chimneys > §27-869 Exhaust Gases From Internal Combustion Engines > §27-869.03 Reduction in Flue Size
504.3.21 Chimneys and Vents, Connector Maximum and Minimum Size
Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter ...
NYC Fuel Gas Code 2014 > 5 Chimneys and Vents > 504 Sizing of Category I Appliance Venting Systems > 504.3 Application of Multiple Appliance Vent Tables 504.3(1) Through 504.3(7) > 504.3.21 Connector Maximum and Minimum Size
504.3.20 Chimneys and Vents, Connector Maximum and Minimum Size
Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter ...