1706.5 Reduced Width of Retrofit Studs
JUMP TO FULL CODE CHAPTER
The broad face of retrofit studs may be reduced in width by methods of cutting, boring, or notching at any number of locations along their length provided that all of the following conditions are met.
- The wide face of retrofit studs shall be sized such that the remaining minimum width of the member at each location of reduced width shall not be less than that required by Table 1704.1.
- The distance between segments of reduced width shall be a minimum of 8 inches (203 mm) and shall be allowable at the ends of retrofit studs.
- The average spacing of fasteners connecting retrofit studs to existing studs shall be maximum 6 inches (152 mm) on center.
- The minimum vertical distance between fasteners on studs shall be a minimum of 23/4 inches. (70 mm).
- Retrofit studs reduced in width shall not be spliced within 12 inches (304.8 mm) of the location of reduced width. Splice members shall not be notched.
Related Code Sections
1706.5 Retrofitting, Reduced Width of Retrofit Studs
The broad face of retrofit studs may be reduced in width by methods of cutting, boring, or notching at any number of locations along their length ...
2014 FBC - Existing Building, 5th edition > 17 Retrofitting > 1706 Retrofit Studs > 1706.5 Reduced Width of Retrofit Studs
1706.5 Retrofitting, Reduced Width of Retrofit Studs
The broad face of retrofit studs may be reduced in width by methods of cutting, boring, or notching at any number of locations along their length ...
2017 FBC - Existing Building, 6th edition > 17 Retrofitting > 1706 Retrofit Studs > 1706.5 Reduced Width of Retrofit Studs
1706.5 Retrofitting, Reduced Width of Retrofit Studs
The broad face of retrofit studs may be reduced in width by methods of cutting, boring, or notching at any number of locations along their length ...
2020 FBC - Existing Building, 7th edition > 17 Retrofitting > 1706 Retrofit Studs > 1706.5 Reduced Width of Retrofit Studs
1706.9 Retrofitting, Spliced Retrofit Studs
-inch lumber with the wide face width equal to or wider than the face width of the spliced retrofit studs. Splice members shall be attached to each ...
2020 FBC - Existing Building, 7th edition > 17 Retrofitting > 1706 Retrofit Studs > 1706.9 Spliced Retrofit Studs
1706.4 Retrofitting, Attachment of Retrofit Studs to Primary Studs
Retrofit studs, nail plates, and nailers shall be fastened in accordance with the following ...
2014 FBC - Existing Building, 5th edition > 17 Retrofitting > 1706 Retrofit Studs > 1706.4 Attachment of Retrofit Studs to Primary Studs