13.6.4.4.2 Record Keeping for Conductivity Testing of Carbon Dioxide Hose Assemblies
Go To Full Code Chapter
13.6.4.4.2.1
Carbon dioxide hose assemblies that pass a conductivity test shall have the test information recorded on a durable weatherproof label that is a minimum of 1/2 in. × 3 in. (13 mm × 76 mm). [10:7.4.2.1]
13.6.4.4.2.2
The label shall be affixed to the hose by means of a heatless process. [10:7.4.2.2]
13.6.4.4.2.3
The label shall include the following information:
- Month and year the test was performed, indicated by perforation such as is done by a hand punch
- Name or initials of person performing the test and the name of the agency performing the test
[10:7.4.2.3]