608.5.2 Recombinant Battery Neutralization
JUMP TO FULL CODE CHAPTER
For VRLA or other types of batteries with immobilized electrolyte, the method and material shall be capable of neutralizing a spill of 3.0 percent of the capacity of the largest cell or block in the room to a pH between 5.0 and 9.0.
Exception:
Lithium-ion and lithium metal polymer batteries shall not require neutralization.
Related Code Sections
608.5.2 Building Services and Systems, Recombinant Battery Neutralization
For VRLA or other types of batteries with immobilized electrolyte, the method and material shall be capable of neutralizing a spill of 3.0 percent ...
Fire Code 2015 of Alabama > 6 Building Services and Systems > 608 Stationary Storage Battery Systems > 608.5 Spill Control and Neutralization > 608.5.2 Recombinant Battery Neutralization
608.5.2 Building Services and Systems, Recombinant Battery Neutralization
For VRLA or other types of sealed batteries with immobilized electrolyte, the method and material shall be capable of neutralizing a spill of 3.0 ...
Fire Code 2009 of Alabama > 6 Building Services and Systems > 608 Stationary Storage Battery Systems > 608.5 Spill Control and Neutralization > 608.5.2 Recombinant Battery Neutralization
1207.6.2.2 Energy Systems, Neutralization
An approved method that is capable of neutralizing spilled liquid electrolyte from the largest battery or vessel to a pH between 5.0 and 9.0 ...
Fire Code 2021 of Alabama > 12 Energy Systems > 1207 Electrical Energy Storage Systems (ESS) > 1207.6 Electrochemical ESS Technology-Specific Protection > 1207.6.2 Spill Control and Neutralization > 1207.6.2.2 Neutralization
608.5.1 Building Services and Systems, Nonrecombinant Battery Neutralization
For battery systems containing lead acid, nickel cadmium or other types of batteries with free-flowing electrolyte, the method and materials shall ...
Fire Code 2015 of Alabama > 6 Building Services and Systems > 608 Stationary Storage Battery Systems > 608.5 Spill Control and Neutralization > 608.5.1 Nonrecombinant Battery Neutralization
608.5 Building Services and Systems, Spill Control and Neutralization
containing lead acid, nickel cadmium or other types of batteries with free-flowing electrolyte, the method and materials shall be capable of neutralizing ...
Fire Code 2015 of Alabama > 6 Building Services and Systems > 608 Stationary Storage Battery Systems > 608.5 Spill Control and Neutralization