// CODE SNIPPET
Section 3126B Recirculation Pump Capacity
JUMP TO FULL CODE CHAPTER
Pool recirculation pumps shall have the following total dynamic head capacities:
- Pressure diatomaceous earth filters. At least 60 feet (18,288 mm); and
- Vacuum diatomaceous earth filters. Twenty inches (508 mm) vacuum on the suction side and 40 feet (12,192 mm) total dynamic head;and
- Rapid sand filters. At least 45 feet (13,716 mm); and
- High rate sand filters. At least 60 feet (18,288 mm); and
- Cartridge filters. At least 60 feet (18,288 mm).
Pumps with other total dynamic head capacities shall be permitted provided the turnover times are maintained as required in Section 3124B.
Related Code Sections
Section 3126B [DPH] Public Pools, Recirculation Pump Capacity
Pool recirculation pumps shall have the following total dynamic head capacities: Pressure diatomaceous earth filters. At least 60 feet (18,288 mm ...
3109.4.4.8 Special Construction, Construction Requirements for Building a Pool or Spa
to conduct water to the recirculation pump. The circulation system shall have the capacity to provide a complete turnover of pool water, as specified ...
Los Angeles Building Code > 31 Special Construction > 3109 Swimming Pool Enclosures and Safety Devices > 3109.4 Residential Swimming Pools > 3109.4.4 Private Swimming Pools (Statewide) > 3109.4.4.8 Construction Requirements for Building a Pool or Spa
AV100.8 Swimming Pool Safety Act, Construction Requirements for Building a Pool or Spa
to conduct water to the recirculation pump. The circulation system shall have the capacity to provide a complete turnover of pool water, as specified ...
Los Angeles Residential Code > V Swimming Pool Safety Act > AV100 Private Swimming Pools (Statewide) > AV100.8 Construction Requirements for Building a Pool or Spa
2404.7.2 Flammable Finishes, Recirculation
Air exhausted from spraying operations shall not be recirculated. Exceptions: Air exhausted from spraying operations is allowed ...
2017 LA City Fire Code > 24 Flammable Finishes > 2404 Spray Finishing > 2404.7 Ventilation > 2404.7.2 Recirculation
516.2.2 Exhaust Systems, Recirculation
Recirculating systems shall be
listed with a testing laboratory in accordance with UL
710B or equivalent. [NFPA 96:13.2.4] ...
Los Angeles Mechanical Code > 5 Exhaust Systems > 516.0 Recirculating Systems > 516.2 Design Restrictions > 516.2.2 Recirculation