Section 612 (IFGC) Recirculating Direct-Firedindustrial Air Heaters
JUMP TO FULL CODE CHAPTER
Recirculating direct-fired industrial air heaters shall be listed to ANSI Z83.18 and shall be installed in accordance with the manufacturer's installation instructions.
Recirculating direct-fired industrial air heaters shall be installed only in industrial and commercial occupancies. Recirculating direct-fired air heaters shall not serve any area containing sleeping quarters. Recirculating direct-fired industrial air heaters shall not be installed in hazardous locations or in buildings that contain flammable solids, liquids or gases, explosive materials or substances that can become toxic when exposed to flame or heat.
Direct-fired industrial air heaters shall be permitted to be installed in accordance with their listing and the manufacturer's instructions. Direct-fired industrial air heaters shall be installed only in industrial or commercial occupancies. Direct-fired industrial air heaters shall be permitted to provide fresh air ventilation.
Direct-fired industrial air heaters shall be installed with a clearance from combustible material of not less than that shown on the label and in the manufacturer's instructions.
Air to direct-fired industrial air heaters shall be taken from the building, ducted directly from outdoors, or a combination of both. Direct-fired industrial air heaters shall incorporate a means to supply outside ventilation air to the space at a rate of not less than 4 cubic feet per minute per 1,000 Btu per hour (0.38 m3 per min per kW) of rated input of the heater. If a separate means is used to supply ventilation air, an interlock shall be provided so as to lock out the main burner operation until the mechanical means is verified. Where outside air dampers or closing louvers are used, they shall be verified to be in the open position prior to main burner operation.
Direct-fired industrial air heaters with valve train components equipped with atmospheric vents, gas reliefs or bleeds shall have their atmospheric vent lines and gas reliefs or bleeds lead to the outdoors.
Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter. An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter.
The design of the installation shall include adequate provision to permit direct-fired industrial air heaters to operate at rated capacity by taking into account the structure's designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a combination of these methods. The structure's designed infiltration rate and the size of relief openings shall be determined by approved engineering methods. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized dampers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation.
Related Code Sections
Section 612 Specific Appliances, (IFGC) Recirculating Direct-Firedindustrial Air Heaters
Recirculating direct-fired industrial air heaters shall be listed to ANSI Z83.18 and shall be installed in accordance with the manufacturer's ...
2012 Virginia Fuel Gas Code > 6 Specific Appliances > 612 (IFGC) Recirculating Direct-Firedindustrial Air Heaters
612.6 Specific Appliances, Atmospheric Vents, Gas Reliefs or Bleeds
Direct-fired industrial air heaters with valve train components equipped with atmospheric vents, gas reliefs or bleeds shall have their atmospheric ...
2012 Virginia Fuel Gas Code > 6 Specific Appliances > 612 (IFGC) Recirculating Direct-Firedindustrial Air Heaters > 612.6 Atmospheric Vents, Gas Reliefs or Bleeds
612.7 Specific Appliances, Relief Opening
The design of the installation shall include adequate provision to permit direct-fired industrial air heaters to operate at rated capacity by taking ...
2012 Virginia Fuel Gas Code > 6 Specific Appliances > 612 (IFGC) Recirculating Direct-Firedindustrial Air Heaters > 612.7 Relief Opening
612.2 Specific Appliances, Location
Recirculating direct-fired industrial air heaters shall be installed only in industrial and commercial occupancies. Recirculating direct-fired air ...
2015 Virginia Fuel Gas Code > 6 Specific Appliances > 612 (IFGC) Recirculating Direct-Fired Industrial Air Heaters > 612.2 Location
612.5 Specific Appliances, Air Supply
Air to direct-fired industrial air heaters shall be taken from the building, ducted directly from outdoors, or a combination of both. Direct-fired ...
2015 Virginia Fuel Gas Code > 6 Specific Appliances > 612 (IFGC) Recirculating Direct-Fired Industrial Air Heaters > 612.5 Air Supply