N1102.4.4 (R402.4.4) Recessed Lighting (Mandatory)
JUMP TO FULL CODE CHAPTER
Recessed luminaires installed in the building thermal
envelope shall be sealed to limit air leakage between conditioned
and unconditioned spaces. All recessed luminaires
shall be IC-rated and labeled as having an air
leakage rate not more than 2.0 cfm (0.944 Lis) when tested
in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure
differential. All recessed luminaires shall be sealed
with a gasket or caulk between the housing and the interior
wall or ceiling covering.
R 408.30547d
R 408.30547d
Related Code Sections
N1102.4.4 [RE] Energy Efficiency, (R402.4.4) Recessed Lighting (Mandatory)
Recessed luminaires installed in the building thermal
envelope shall be sealed to limit air leakage between conditioned
and unconditioned spaces. All ...
2015 Michigan Residential Code > 11 [RE] Energy Efficiency > N1102 Building Thermal Envelope > N1102.4 (R402.4) Air Leakage > N1102.4.4 (R402.4.4) Recessed Lighting (Mandatory)
N1104.1 [RE] Energy Efficiency, (R404.1) Lighting Equipment (Mandatory)
A
minimum of 75 percent of the lamps in permanently installed
lighting fixtures shall be high-efficacy lamps or a minimum
of 75 percent ...
2015 Michigan Residential Code > 11 [RE] Energy Efficiency > N1104 Electrical Power and Lighting Systems (Mandatory) > N1104.1 (R404.1) Lighting Equipment (Mandatory)
Appendix R Light Straw-Clay Construction
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance ...
R302.13 Building Planning, Combustible Insulation
Combustible insulation shall be separated a minimum of 3 inches (76 mm) from
recessed lighting fixtures, fan motors, and other heat-producing devices ...
2015 Michigan Residential Code > 3 Building Planning > R302 Fire-Resistant Construction > R302.13 Combustible Insulation
E3907.5 Power and Lighting Distribution, Unused Openings
used with nonmetallic cabinets shall be recessed at least 1 / 4 inch (6.4 mm) from the outer surface. Unused openings for circuit breakers ...
2015 Michigan Residential Code > 39 Power and Lighting Distribution > E3907 Cabinets and Panelboards > E3907.5 Unused Openings