// CODE SNIPPET
5.8.1.6 Recessed Equipment
Go To Full Code Chapter
Lighting fixtures; heating, ventilating, and air-conditioning equipment, including wall heaters, ducts, and plenums; and other equipment shall not be recessed in such a manner as to affect the insulation thickness unless
- the total combined area affected (including necessary clearances) is less than 1% of the opaque area of the assembly,
- the entire roof, wall, or floor is covered with insulation to the full depth required, or
- the effects of reduced insulation are included in calculations using an area-weighted-average method and compressed insulation values obtained from Table A9.4.3.
In all cases, air leakage through or around the recessed equipment to the conditioned space shall be limited in accordance with Section 5.4.3.
Related Code Sections
5.8.1.6 Building Envelope, Recessed Equipment
In all cases, air leakage through or around the recessed equipment to the conditioned space shall be limited in accordance with Section 5.4.3 ...
520.72 Special Occupancies, Lamp Guards
guards riveted to the outlet box cover or otherwise sealed or locked in place. Recessed lamps shall not be required to be equipped with guards ...
(1) Equipment for General Use, Recessed
Recessed high-intensity luminaires designed to be installed in wall or ceiling cavities shall have thermal protection and be identified as thermally ...
(1) Special Occupancies, Separable
be equipped with a permanently mounted, flanged surface inlet (male, recessed-type motor-base attachment plug) wired directly to the panelboard ...
(A) General, Unused Openings
Unused openings, other than those intended for the operation of equipment, those intended for mounting purposes, or those permitted as part ...