604.5.2 Rear Wall Grab Bars
JUMP TO FULL CODE CHAPTER
The rear wall grab bar shall be 36 inches (915 mm) minimum in length, and extend from the centerline of the water closet 12 inches (305 mm) minimum on the side closest to the wall, and 24 inches (610 mm) minimum on the transfer side.
Exceptions:
- The rear grab bar shall be permitted to be 24 inches (610 mm) minimum in length, centered on the water closet, where wall space does not permit a grab bar 36 inches (915 mm) minimum in length due to the location of a recessed fixture adjacent to the water closet.
- Where an administrative authority requires flush controls for flush valves to be located in a position that conflicts with the location of the rear grab bar, that grab bar shall be permitted to be split or shifted to the open side of the toilet area.
Note: For children's dimensions see Figure 609.4.2 |
FIGURE 604.5.2
REAR WALL GRAB BAR FOR WATER CLOSET
Related Code Sections
604.5.2 Plumbing Elements and Facilities, Rear Wall Grab Bars
The rear wall grab bar shall be 36 inches (915 mm) minimum in length, and extend from the centerline of the water closet 12 inches (305 mm) minimum ...
Minnesota Accessibility Code 2015 > 6 Plumbing Elements and Facilities > 604 Water Closets and Toilet Compartments > 604.5 Grab Bars > 604.5.2 Rear Wall Grab Bars
1004.11.1 Dwelling Units and Sleeping Units, Grab Bar and Shower Seat Reinforcement
water closets where wall space will not permit a grab bar complying with Section 604.5.2, reinforcement for a rear wall grab bar 24 inches (610 mm ...
Minnesota Accessibility Code 2015 > 10 Dwelling Units and Sleeping Units > 1004 Type B Units > 1004.11 Toilet and Bathing Facilities > 1004.11.1 Grab Bar and Shower Seat Reinforcement
604.5.1.2 Plumbing Elements and Facilities, Vertical Fixed Side Wall Grab Bars
Vertical fixed side wall grab bars shall be 18 inches (455 mm) minimum in length and shall be mounted with the bottom of the bar located 39 inches ...
Minnesota Accessibility Code 2015 > 6 Plumbing Elements and Facilities > 604 Water Closets and Toilet Compartments > 604.5 Grab Bars > 604.5.1 Fixed Side Wall Grab Bars > 604.5.1.2 Vertical Fixed Side Wall Grab Bars
1004.11 Dwelling Units and Sleeping Units, Toilet and Bathing Facilities
with Section 604.5.2, reinforcement for a rear wall grab bar 24 inches (610 mm) minimum in length centered on the water closet shall be provided. At ...
Minnesota Accessibility Code 2015 > 10 Dwelling Units and Sleeping Units > 1004 Type B Units > 1004.11 Toilet and Bathing Facilities
604.7 Plumbing Elements and Facilities, Dispensers
the grab bar, the outlet of the dispenser shall be located within an area 24 inches (610 mm) minimum and 42 inches (1065 mm) maximum from the rear wall. The ...
Minnesota Accessibility Code 2015 > 6 Plumbing Elements and Facilities > 604 Water Closets and Toilet Compartments > 604.7 Dispensers