430.83 Ratings
JUMP TO FULL CODE CHAPTER
The controller shall have a rating as specified in 430.83(A), unless otherwise permitted in 430.83(B) or (C), or as specified in (D), under the conditions specified.
Controllers, other than inverse time circuit breakers and molded case switches, shall have horsepower ratings at the application voltage not lower than the horsepower rating of the motor.
A branch-circuit inverse time circuit breaker rated in amperes shall be permitted as a controller for all motors. Where this circuit breaker is also used for overload protection, it shall conform to the appropriate provisions of this article governing overload protection.
A molded case switch rated in amperes shall be permitted as a controller for all motors.
For stationary motors rated at 2 hp or less and 300 volts or less, the controller shall be permitted to be either of the following:
- A general-use switch having an ampere rating not less than twice the full-load current rating of the motor
- On ac circuits, a general-use snap switch suitable only for use on ac (not general-use ac-dc snap switches) where the motor full-load current rating is not more than 80 percent of the ampere rating of the switch
For torque motors, the controller shall have a continuous-duty, full-load current rating not less than the nameplate current rating of the motor. For a motor controller rated in horsepower but not marked with the foregoing current rating, the equivalent current rating shall be determined from the horsepower rating by using Table 430.247, Table 430.248, Table 430.249, or Table 430.250.
A controller with a straight voltage rating, for example, 240 volts or 480 volts, shall be permitted to be applied in a circuit in which the nominal voltage between any two conductors does not exceed the controller's voltage rating. A controller with a slash rating, for example, 120/240 volts or 480Y/277 volts, shall only be applied in a solidly grounded circuit in which the nominal voltage to ground from any conductor does not exceed the lower of the two values of the controller's voltage rating and the nominal voltage between any two conductors does not exceed the higher value of the controller's voltage rating.
Related Code Sections
210.18 Wiring and Protection, Rating
Branch circuits recognized by this article shall be rated in accordance with the maximum permitted ampere rating or setting of the overcurrent device ...
National Electrical Code 2017 of Illinois > 2 Wiring and Protection > 210 Branch Circuits > 210.18 Rating
210.18 Wiring and Protection, Rating
Branch circuits recognized by this article shall be rated in accordance with the maximum permitted ampere rating or setting of the overcurrent device ...
National Electrical Code 2020 of Illinois > 2 Wiring and Protection > 210 Branch Circuits > 210.18 Rating
(A) Wiring and Protection, Rating
The rating of a surge arrester shall be equal to or greater than the maximum continuous operating voltage available at the point of application ...
National Electrical Code 2020 of Illinois > 2 Wiring and Protection > 242 Overvoltage Protection > 242.42 Surge Arrester Selection > (A) Rating
(A) Wiring and Protection, Rating
The rating of a surge arrester shall be equal to or greater than the maximum continuous operating voltage available at the point of application ...
National Electrical Code 2017 of Illinois > 2 Wiring and Protection > 280 Surge Arresters, Over 1000 Volts > 280.4 Surge Arrester Selection > (A) Rating
(A) Equipment for General Use, Ratings
Switches shall be marked with the current, voltage, and, if horsepower rated, the maximum rating for which they are designed ...
National Electrical Code 2020 of Illinois > 4 Equipment for General Use > 404 Switches > 404.20 Marking > (A) Ratings