// CODE SNIPPET
210.18 Rating
Go To Full Code Chapter
Branch circuits recognized by this article shall be rated in accordance with the maximum permitted ampere rating or setting of the overcurrent device. The rating for other than individual branch circuits shall be 15, 20, 30, 40, and 50 amperes. Where conductors of higher ampacity are used for any reason, the ampere rating or setting of the specified overcurrent device shall determine the circuit rating.
Exception: Multioutlet branch circuits greater than 50 amperes shall be permitted to supply nonlighting outlet loads on industrial premises where conditions of maintenance and supervision ensure that only qualified persons service the equipment.
Related Code Sections
210.18 Wiring and Protection, Rating
Branch circuits recognized by this article shall be rated in accordance with the maximum permitted ampere rating or setting of the overcurrent device ...
210.18 Wiring and Protection, Rating
Branch circuits recognized by this article shall be rated in accordance with the maximum permitted ampere rating or setting of the overcurrent device ...
(A) Wiring and Protection, Rating
The rating of a surge arrester shall be equal to or greater than the maximum continuous operating voltage available at the point of application ...
(A) Wiring and Protection, Rating
The rating of a surge arrester shall be equal to or greater than the maximum continuous operating voltage available at the point of application ...
(A) Equipment for General Use, Ratings
Switches shall be marked with the current, voltage, and, if horsepower rated, the maximum rating for which they are designed ...