1217.2 Radiant Under-Floor Heating
JUMP TO FULL CODE CHAPTER
Floor finished surface
temperatures shall not exceed the following temperatures for space heating applications:
- 85°F (29°C) in general occupied applications.
- 90°F (32°C) in bathrooms, foyers, distribution areas such as hallways and indoor swimming pools.
- 88°F (31°C) in industrial spaces
- 95°F (35°C) in radiant panel perimeter areas, i.e., up to 2.5 feet (762 mm) from outside walls.
Related Code Sections
1217.2 Hydronics, Radiant Under-Floor Heating
The radiant heating panel temperature shall not exceed
the maximum temperature rating of the materials used in the
construction ...
California Mechanical Code 2016 > 12 Hydronics > 1217.0 Radiant Heating and Cooling > 1217.2 Radiant Under-Floor Heating
1217.2 Hydronics, Radiant Under-Floor Heating
Floor finished surface
temperatures shall not exceed the following temperatures for space heating applications:
85°F (29°C) in general occupied ...
California Mechanical Code 2019 > 12 Hydronics > 1217.0 Radiant Heating and Cooling > 1217.2 Radiant Under-Floor Heating
1213.2 Hydronics, Radiant Floor Heating Panels
Radiant floor heating
panels shall be protected with a high-limit control set 20°F
(11°C) above the maximum design water temperature for the
panel ...
California Mechanical Code 2016 > 12 Hydronics > 1213.0 System Controls > 1213.2 Radiant Floor Heating Panels