Section M1406 Radiant Heating Systems
JUMP TO FULL CODE CHAPTER
Radiant panels installed on wood framing shall conform to the following requirements:
- Heating panels shall be installed parallel to framing members and secured to the surface of framing members or mounted between framing members.
- Mechanical fasteners shall penetrate only the unheated portions provided for this purpose. Panels shall not be fastened at any point closer than 1/4 inch (6.4 mm) to an element. Other methods of attachment of the panels shall be in accordance with the panel manufacturer's instructions.
- Unless listed and labeled for field cutting, heating panels shall be installed as complete units.
Radiant heating systems installed in concrete or masonry shall conform to the following requirements:
- Radiant heating systems shall be identified as being suitable for the installation, and shall be secured in place as specified in the manufacturer's installation instructions.
- Radiant heating panels or radiant heating panel sets shall not be installed where they bridge expansion joints unless protected from expansion and contraction.
Finish materials installed over radiant heating panels or systems shall be installed in accordance with the manufacturer's instructions. Surfaces shall be secured so that nails or other fastenings do not pierce the radiant heating elements.
Related Code Sections
Section 927 Specific Appliances, Fireplaces and Solid Fuel-Burning Equipment, Radiant Heating Systems
Electric radiant heating systems shall be installed in accordance with the manufacturer's instructions and shall be listed for the application ...
Mechanical Code 2018 of Kansas > 9 Specific Appliances, Fireplaces and Solid Fuel-Burning Equipment > 927 Radiant Heating Systems
Section M1406 Heating and Cooling Equipment and Appliances, Radiant Heating Systems
Electric radiant heating systems shall be installed in accordance with the manufacturer's instructions and Chapters 34 through 43 and shall be listed ...
Residential Code 2018 of Kansas > 14 Heating and Cooling Equipment and Appliances > M1406 Radiant Heating Systems
C402.2.6 [CE] Commercial Energy Efficiency, Insulation of Radiant Heating Systems
Radiant heating system panels, and their associated components that are installed in interior or exterior assemblies shall be insulated to an R ...
Energy Conservation Code 2018 of Kansas > 4 [CE] Commercial Energy Efficiency > C402 Building Envelope Requirements > C402.2 Specific Building Thermal Envelope Insulation Requirements (Prescriptive) > C402.2.6 Insulation of Radiant Heating Systems
927.4 Specific Appliances, Fireplaces and Solid Fuel-Burning Equipment, Installation in Concrete or Masonry
Radiant heating systems installed in concrete or masonry shall conform to the following requirements: Radiant heating systems shall be identified ...
Mechanical Code 2018 of Kansas > 9 Specific Appliances, Fireplaces and Solid Fuel-Burning Equipment > 927 Radiant Heating Systems > 927.4 Installation in Concrete or Masonry
927.5 Specific Appliances, Fireplaces and Solid Fuel-Burning Equipment, Finish Surfaces
Finish materials installed over radiant heating panels and systems shall be installed in accordance with the manufacturer's instructions. Surfaces ...
Mechanical Code 2018 of Kansas > 9 Specific Appliances, Fireplaces and Solid Fuel-Burning Equipment > 927 Radiant Heating Systems > 927.5 Finish Surfaces