5104.4.3 Rack Storage Aisles
JUMP TO FULL CODE CHAPTER
Rack storage shall be arranged with a minimum aisle width of 8 feet (2438 mm) between rows of racks and 8 feet (2438 mm) between racks and adjacent solid pile or palletized storage. Where early suppression fast-response (ESFR) sprinklers provide automatic sprinkler protection, the minimum aisle width shall be 4 feet (1219 mm).
Related Code Sections
5104.4.3 Aerosols, Rack Storage Aisles
Rack storage shall be arranged with a minimum aisle width of 8 feet (2438 mm) between rows of racks and 8 feet (2438 mm) between racks and adjacent ...
Fire Code 2021 of Colorado > 51 Aerosols > 5104 Inside Storage of Aerosol Products > 5104.4 Storage in Aerosol Product Warehouses > 5104.4.3 Rack Storage Aisles
5104.4.3 Aerosols, Rack Storage Aisles
Rack storage shall be arranged with a minimum aisle width of 8 feet (2438 mm) between rows of racks and 8 feet (2438 mm) between racks and adjacent ...
Fire Code 2018 of Colorado > 51 Aerosols > 5104 Inside Storage of Aerosol Products > 5104.4 Storage in Aerosol Product Warehouses > 5104.4.3 Rack Storage Aisles
20.5.3.2.1 General Requirements for Storage,
Aisles required by Chapters 21 through 25 shall not be obstructed unless Chapters 21 through 25 include specific guidance allowing obstructions over ...
Standard for the Installation of Sprinkler Systems 2019 of Colorado > 20 General Requirements for Storage > 20.5 Storage Arrangement > 20.5.3* Rack Storage > 20.5.3.2 Aisles > 20.5.3.2.1
20.5.3 Special Designs of Storage Protection,
Each storage rack shall be separated from other storage racks by aisles that are not less than 30 ...
Standard for the Installation of Sprinkler Systems 2013 of Colorado > 20 Special Designs of Storage Protection > 20.5 Sprinkler Protection of Carton Records Storage With Catwalk Access > 20.5.3
20.5.3 Special Designs of Storage Protection,
Each storage rack shall be separated from other storage racks by aisles that are not less than 30 ...
Standard for the Installation of Sprinkler Systems 2016 of Colorado > 20 Special Designs of Storage Protection > 20.5 Sprinkler Protection of Carton Records Storage With Catwalk Access > 20.5.3