// CODE SNIPPET
1225.4.1.11 Quiet Room
JUMP TO FULL CODE CHAPTER
If a quiet room is provided, the
quiet room shall comply with the following requirements.
Refer to Section
1225.5.1.2, Nursing service space.
Provide a patient toilet
room adjacent to the quiet room. The patient toilet
room shall not be shared with another patient room.
If the quiet room is located in a common area, the
patient toilet room may be shared with compatible
services or activities.
The quiet room shall
comply with the acoustic requirements of Section
1224.4.19, Noise control.
Related Code Sections
1225.4.1.11 Interior Environment, Quiet Room
If a quiet room is provided, the
quiet room shall comply with the following requirements ...
Los Angeles Building Code > 12 Interior Environment > 1225 [OSHPD 2] Skilled Nursing and Intermediate-Care Facilities > 1225.4 Common Elements > 1225.4.1 Nursing Service Space > 1225.4.1.11 Quiet Room
1228.14.6 Interior Environment, Quiet Room
A quiet room shall be provided in
each psychiatric nursing unit for a patient who needs to be
alone for a short period of time but does not require ...
Los Angeles Building Code > 12 Interior Environment > 1228 Acute Psychiatric Hospitals > 1228.14 Psychiatric Nursing Service Space > 1228.14.6 Quiet Room
1228.4.4.1 Interior Environment, Examination and Treatment Rooms
1224.4.4.1.4. Where provided, a quiet
room for a single ...
Los Angeles Building Code > 12 Interior Environment > 1228 Acute Psychiatric Hospitals > 1228.4 General Construction > 1228.4.4 Support Areas for Patients > 1228.4.4.1 Examination and Treatment Rooms
1228.4.4 Interior Environment, Support Areas for Patients
1224.4.4.1.4. Where provided, a quiet
room for a single ...
Los Angeles Building Code > 12 Interior Environment > 1228 Acute Psychiatric Hospitals > 1228.4 General Construction > 1228.4.4 Support Areas for Patients
1225.4 Interior Environment, Common Elements
If a quiet room is provided, the
quiet room shall comply with the following ...
Los Angeles Building Code > 12 Interior Environment > 1225 [OSHPD 2] Skilled Nursing and Intermediate-Care Facilities > 1225.4 Common Elements