3418A.4.1 Qualifying Nonacute Care Services
JUMP TO FULL CODE CHAPTER
In order for a freestanding building to remain under OSHPD jurisdiction that is removed from general acute care service, it shall contain one or more qualifying services. Qualifying services include:
- Services considered "Outpatient Clinical Services" as defined in H&SC §129730 (a):
- Administrative space
- Central sterile supply
- Storage
- Morgue and autopsy facilities
- Employee dressing rooms and lockers
- Janitorial and housekeeping facilities
- Laundry
- Outpatient portions of the following services (with no more than 25 percent in-patient use), including but not limited to:
- Surgical
- Chronic dialysis
- Psychiatry
- Rehabilitation, occupational therapy or physical therapy
- Maternity
- Dentistry
- Chemical dependency
- Services that duplicate Basic Services, as defined in H&SC§1250, or services that are provided as part of a Basic Service, but are not required for facility licensure (with no more than 25 percent in-patient use).
All hospital support services listed in Section 3418A.4.1 Item a that are located in an SPC building at the time general acute care services are removed may remain, provided the California Department of Public Health certifies to the Office that it has received and approved a plan that demonstrates how the health facility will continue to provide all basic services in the event of any emergency when the SPC building may no longer remain functional. This certification shall be submitted by hospital to the Office prior to approval of the application to remove the SPC building from general acute care service.
Related Code Sections
3418A.4.1 Existing Structures, Qualifying Nonacute Care Services
In order for a freestanding building to remain under OSHPD jurisdiction that is removed from general acute care service, it shall contain one ...
California Building Code 2016 (Vol 1 & 2) > 34A Existing Structures > 3418A Removal of Hospital Buildings From General Acute Care Services > 3418A.4 Buildings Intended to Remain Under OSHPD Jurisdiction > 3418A.4.1 Qualifying Nonacute Care Services
309.3.1 Provisions for All Compliance Methods, Freestanding Buildings Containing Qualifying Nonacute Care Services
service, to remain under OSHPD jurisdiction, it shall contain one or more qualifying nonacute care services. Qualifying nonacute care services include ...
California Existing Building Code 2019 > 3 Provisions for All Compliance Methods > 309 [OSHPD 1R] Hospital SPC and Freestanding Buildings Removed From General Acute Care Service Remaining Under the Jurisdiction of OSHPD > 309.3 Buildings to Remain Under OSHPD Jurisdiction. > 309.3.1 Freestanding Buildings Containing Qualifying Nonacute Care Services
307A.1.1.1.5 Provisions for All Compliance Methods, Buildings Removed From Acute-Care Hospital Service
1.1.1.1. Services/systems and utilities for nonconforming nonacute care hospital buildings shall be permitted to pass through or under a building ...
California Existing Building Code 2019 > 3A Provisions for All Compliance Methods > 307A Compliance Alternatives for Services/Systems and Utilities > 307A.1 General > 307A.1.1 Services/Systems and Utilities > 307A.1.1.1 Services/Systems and Utilities for Hospital Buildings > 307A.1.1.1.5 Buildings Removed From Acute-Care Hospital Service
307A.1.1.1 Provisions for All Compliance Methods, Services/Systems and Utilities for Hospital Buildings
nonacute care hospital buildings shall be permitted to pass through or under a building that has been removed from acute care hospital service only ...
California Existing Building Code 2019 > 3A Provisions for All Compliance Methods > 307A Compliance Alternatives for Services/Systems and Utilities > 307A.1 General > 307A.1.1 Services/Systems and Utilities > 307A.1.1.1 Services/Systems and Utilities for Hospital Buildings
307A.1.1 Provisions for All Compliance Methods, Services/Systems and Utilities
removed from service meets the performance requirements of Section 307A.1.1.1.1. Services/systems and utilities for nonconforming nonacute care ...
California Existing Building Code 2019 > 3A Provisions for All Compliance Methods > 307A Compliance Alternatives for Services/Systems and Utilities > 307A.1 General > 307A.1.1 Services/Systems and Utilities