6404.1.2 Pyrophoric Solids and Liquids
JUMP TO FULL CODE CHAPTER
Storage of pyrophoric solids and liquids shall be limited to a maximum area of 100 square feet (9.3 m2) per pile. Storage shall not exceed 5 feet (1524 mm) in height. Individual containers shall not be stacked.
Aisles between storage piles shall be not less than 10 feet (3048 mm) in width.
Individual tanks or containers shall not exceed 500 gallons (1893 L) in capacity.
Related Code Sections
6404.1.2 Pyrophoric Materials, Pyrophoric Solids and Liquids
Storage of pyrophoric solids and liquids shall be limited to a maximum area of 100 square feet (9.3 m 2 ) per pile. Storage shall not exceed 5 feet ...
Fire Code 2018 of Kansas > 64 Pyrophoric Materials > 6404 Storage > 6404.1 Indoor Storage > 6404.1.2 Pyrophoric Solids and Liquids
2705.2.3.4 Semiconductor Fabrication Facilities, Pyrophoric Solids, Liquids and Class 3 Water-Reactive Liquids
Pyrophoric liquids and Class 3 water-reactive liquids in containers greater than 0.5-gallon (2 L) but not exceeding 5.3-gallon (20 L) capacity ...
Fire Code 2018 of Kansas > 27 Semiconductor Fabrication Facilities > 2705 Use and Handling > 2705.2 Fabrication Areas > 2705.2.3 Workstations > 2705.2.3.4 Pyrophoric Solids, Liquids and Class 3 Water-Reactive Liquids
5001.2.2.1 Hazardous Materials—General Provisions, Physical Hazards
solids or liquids. Oxidizer, solids or liquids. Oxidizing gases. Pyrophoric solids, liquids or gases. Unstable (reactive) solids, liquids or gases ...
Fire Code 2018 of Kansas > 50 Hazardous Materials—General Provisions > 5001 General > 5001.2 Material Classification > 5001.2.2 Hazard Categories > 5001.2.2.1 Physical Hazards
6404.2 Pyrophoric Materials, Outdoor Storage
The separation of pyrophoric solids, liquids and gases from buildings, lot lines , public streets, public alleys, public ways ...
415.8.4 Special Detailed Requirements Based on Occupancy and Use, Floors in Storage Rooms
Floors in storage areas for organic peroxides, oxidizers, pyrophoric materials, unstable (reactive) materials and water-reactive solids and liquids ...
Building Code 2018 of Kansas > 4 Special Detailed Requirements Based on Occupancy and Use > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.8 Special Provisions for Group H-2 and H-3 Occupancies > 415.8.4 Floors in Storage Rooms