[F] 902.1 Pump and Riser Room Size
JUMP TO FULL CODE CHAPTER
Where provided, fire pump rooms and automatic sprinkler system riser rooms shall be designed with adequate space for all equipment necessary for the installation, as defined by the manufacturer, with sufficient working room around the stationary equipment. Clearances around equipment to elements of permanent construction, including other installed equipment and appliances, shall be sufficient to allow inspection, service, repair or replacement without removing such elements of permanent construction or disabling the function of a required fire-resistance-rated assembly. Fire pump and automatic sprinkler system riser rooms shall be provided with doors and unobstructed passageways large enough to allow removal of the largest piece of equipment.
Automatic sprinkler system risers, fire pumps and controllers shall be provided with ready access. Where located in a fire pump room or automatic sprinkler system riser room, the door shall be permitted to be locked provided that the key is available at all times.
Access doors for automatic sprinkler system riser rooms and fire pump rooms shall be labeled with an approved sign. The lettering shall be in contrasting color to the background. Letters shall have a minimum height of 2 inches (51 mm) with a minimum stroke of 3/8 inch (10 mm).
Automatic sprinkler system riser rooms and fire pump rooms shall be maintained at a temperature of not less than 40°F (4°C). Heating units shall be permanently installed.
Permanently installed artificial illumination shall be provided in the automatic sprinkler system riser rooms and fire pump rooms.
Related Code Sections
902.1 Fire Protection and Life Safety Systems, Pump and Riser Room Size
Where provided, fire pump rooms and automatic sprinkler system riser rooms shall be designed with adequate space for all equipment necessary ...
Building Code 2021 of Illinois > 9 Fire Protection and Life Safety Systems > 902 Fire Pump and Riser Room Size > 902.1 Pump and Riser Room Size
902.1 Fire Protection and Life Safety Systems, Pump and Riser Room Size
Where provided, fire pump rooms and automatic sprinkler system riser rooms shall be designed with adequate space for all equipment necessary ...
Building Code 2018 of Illinois > 9 Fire Protection and Life Safety Systems > 902 Fire Pump and Riser Room Size > 902.1 Pump and Riser Room Size
902.1.3 Fire Protection and Life Safety Systems, Environment
Automatic sprinkler system riser rooms and fire pump rooms shall be maintained at a temperature of not less than 40°F (4°C). Heating units shall ...
Building Code 2018 of Illinois > 9 Fire Protection and Life Safety Systems > 902 Fire Pump and Riser Room Size > 902.1 Pump and Riser Room Size > 902.1.3 Environment
902.1.1 Fire Protection and Life Safety Systems, Access
Automatic sprinkler system risers, fire pumps and controllers shall be provided with ready access. Where located in a fire pump room or automatic ...
Building Code 2021 of Illinois > 9 Fire Protection and Life Safety Systems > 902 Fire Pump and Riser Room Size > 902.1 Pump and Riser Room Size > 902.1.1 Access
902.1.1 Fire Protection and Life Safety Systems, Access
Automatic sprinkler system risers, fire pumps and controllers shall be provided with ready access. Where located in a fire pump room or automatic ...
Building Code 2018 of Illinois > 9 Fire Protection and Life Safety Systems > 902 Fire Pump and Riser Room Size > 902.1 Pump and Riser Room Size > 902.1.1 Access